| 2015-12-23 10:36:34 | RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION (2014) |
| | |
| | 1- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING |
| | CALCULATIONS TO PROVIDE ALL HIS INFORMATION AS REQUIRED |
| | BY F.A.C. SEC. 61G15-23.002 AND F.S. 471. |
| | |
| | 2- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING |
| | CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY F.A.C. SEC. 61G15-23.002. AND F.S. 471. |
| | |
| | 3- SEC. R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014) DOESN'T ALLOW ANY ADDITIONAL FACTORS |
| | THAT WILL AFFECT THE A/C EQUIPMENT SIZING. EQUIPMENT |
| | SIZING CALCULATIONS SUBMITTED ARE DONE BASED ON AN |
| | OCCUPANT LOAD OF 8 PEOPLE. 8 PEOPLE IS NOT THE TYPICAL |
| | NUMBER OF PEOPLE FOR A 2 BEDROOM HOUSE. ENERGY |
| | CALCULATIONS SUBMITTED ARE MORE REALISTIC AND SHOW 4 |
| | OCCUPANTS. REVISE CALCULATIONS AS REQUIRED. |
| | |
| | 4- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES |
| | THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). CALCULATIONS |
| | SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21441 |
| | BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR |
| | 2.4 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED. |
| | |
| | 5- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1. |
| | EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING |
| | CALCULATIONS AS REQUIRED BY ITEMS #3 AND #4 ABOVE. SEC. |
| | R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | 6- SHEET M.1: TRANSFER DUCT SIZE SPECIFIED FOR BEDROOMS |
| | #1 AND #2 DOESN'T COMPLY WITH THE BALANCED RETURN AIR |
| | SEC. M 1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | REVISE AS REQUIRED. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD |
| | PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR |
| | REFERENCE. |
| | |