| 2015-12-23 15:32:14 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | MIKE ALBARRAN |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | PROVISO |
| | |
| | (C) BOXES AT CEILING-SUSPENDED (PADDLE) FAN OUTLETS. |
| | OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| | SUPPORT |
| | OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED, |
| | SHALL BE |
| | MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS |
| | PURPOSE, |
| | AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| | THAT |
| | WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR |
| | OUTLET BOX |
| | SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) |
| | FANS |
| | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL |
| | INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. |
| | |
| | R404.1 LIGHTING EQUIPMENT (MANDATORY). |
| | A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS. |
| | |
| | R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| | MM) OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| | |
| | |