| 2015-11-19 06:25:09 | 1) SHOW THE EHD NUMBER OF THE CSST FOR EACH PIPE SIZE |
| | BEING USED.WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS |
| | APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE. |
| | COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5 |
| | THROUGH G2407.11. |
| | 3) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS.IT |
| | APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO |
| | FBC SEC. 107.1, ALL APPLIANCES SHALL BE LISTED AND |
| | LABELED PER 2014 FBCR SEC.G2404.3. |
| | 4) THE 1/2 " GALVANIZED DROP TO THE SUMMER KITCHEN |
| | SHALL BE 3/4". TABLE 402.4(2) FGC. |
| | 5) THE 1/2" CSST TO THE SUMMER KITCHEN SHALL BE 3/4". |
| | TABLE 402.4(15) FGC. |
| | 6) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL |
| | BE 1". TABLE 402.4(15) FGC. |
| | 7) THE PE TO THE POOL HEATER SHALL BE 1 1/2 ". TABLE |
| | 402.4 (21) FGC. |
| | 8) THE PLANS REFER TO TABLE 402.4 (2) FOR PE PIPE. THIS |
| | TABLE IS FOR SCH. 40 METALLIC PIPE. INDICATE THE |
| | CORRECT SIZING TABLES FOR ALL THE DIFFERENT TYPE OF |
| | PIPE MATERIAL ON THE PLANS. |
| | 9) IF ANY MP REGULATORS ARE GOING TO BE INSTALLED, SHOW |
| | THE LOCATION ON THE PLANS AND LIST THE CORRECT SIZING |
| | TABLE FOR THE SYSTEM. |
| | 10) THE BTU LOAD OF THE APPLIANCES ON THE GAS TABLE DO |
| | NOT CORRELATE WITH THE RISER DIAGRAM. CLARIFY. |
| | 11) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT |
| | SHOW THAT THE RANGE IS LISTED OR LABELED PER 2010 |
| | FBC-RES. SEC. G2404.3. THE SUBMITTED DOCUMENT IS |
| | NOTHING MORE THAN AN INTERNET SALES SHEET. |
| | 12) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT |
| | SHALL BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES. |
| | SEC. G 2408.1. |
| | 13) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN |
| | THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF |
| | PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF |
| | PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 & |
| | G2427. |
| | |