| 2015-11-24 15:13:25 | MECHANICAL PRVISOS | | | PERMIT #15110669 | | | 11/24/15 | | | | | | 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE GREASE DUCT AND DUCT WRAP SHALL BE | | | ON-SITE AT TIME OF INSPECTION. | | | 2) A PERMANENT MEANS OF ACCESS SHALL BE PROVIDED TO | | | SERVICE, REPAIR, OR REPLACE THE ROOF TOP EQUIPMENT- | | | SECTION 306.4 FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|