| Plan Review Notes For Permit 15110669 |
| Permit Number |
15110669 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-20 07:41:49 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15110669 | | | 11/20/15 | | | | | | 1) SHEET 3: THE PLAN INDICATES TWO DIFFERENT TYPE OF | | | GREASE DUCT ASSEMBLIES- WELDED DUCT IS INDICATED IN THE | | | GENERAL NOTES AND ALSO NOTED AT THE BOTTOM OF THE | | | SHEET; AND MECHANICALLY CONNECTED USING AN ETL LISTED | | | TO UL-1978 PRODUCT. PLEASE CHOOSE ONE METHOD OR THE | | | OTHER AND REVISE THE SHEET. PLEASE NOTE THAT | | | MANUFACTRURER'S SPECIIFCATIONS AND INSTALLATION | | | INSTRUCTIONS MUST BE SUBMITTED FOR THE UL LISTED DUCT. | | | 2) THE PLAN INDICATES THE GREASE DUCT WILL HAVE 0 | | | CLEARANCE TO THE COMBUSTIBLE ROOF MATERIAL: HOW WILL | | | THAT BE ACCOMPLISHED? IF DUCT WRAP IS TO BE USED, | | | PROVIDE DETAILS ON SHEET 3. | | | 3) I AM CHALLENGING THE $7000.00 PROJECT VALUE LISTED | | | ON THE PERMIT APPLICATION IN ACCORDANCE WITH SECTION | | | 109.3 WPB AMENDMENTS TO THE FBC-14 BUILDING CODE. | | | PERMIT VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT , | | | DESIGN FEES, OVERHEAD AND PROFIT. PLEASE PROVIDE | | | DOCUMENTATION OF COSTS AND ADJUST THE VALUE ON THE | | | APPLICATION ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|