| 2015-11-20 10:19:18 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | |
| | PLEASE PROVIDE AN ELECTRICAL PLAN PER FBC 107 TO |
| | DEMONSTRATE THE EXISTING ELECTRICAL SYSTEM CAN |
| | ACCOMODATE THE ADDED LOAD FOR NEW ELECTRICAL |
| | INSTALLATIONS AND SHOW THE PROPOSED LOCATION OF |
| | ELECTRICAL DEVICES. PROVIDE AN ELECTRICAL PANEL |
| | SCHEDULE. DEMONSTRATE COMPLIANCE WITH THE FOLLOWING: |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH SLEEPING ROOM IF APPLICABLE. |
| | |
| | E3901.2.1 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| | OUTLET. |
| | |
| | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | FBCRE3903.3 ADDITIONAL LOCATIONS. |
| | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED |
| | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT |
| | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL |
| | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR |
| | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL |
| | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED |
| | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A |
| | VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN |
| | OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS |
| | ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A |
| | WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT |
| | INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS |
| | WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE |
| | RISERS. |
| | |
| | FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |