| 2015-11-23 07:44:42 | 1ST REVIEW 2014 MECHANICAL |
| | PERMIT #15110637 |
| | 11/23/15 |
| | |
| | 1) IN ACCORDANCE WITH SECTION 202 FBC-14 ENERGY |
| | CONSERVATION, THE PROPOSED PROJECT IS DEFINED AS A |
| | "RENOVATION" AND SHALL BE IN COMPLIANCE WITH THE |
| | CURRENT FL. ENERGY CODE. PLEASE SEE SECTION C101.4.3 |
| | AND SUBMIT ENERGY CALCULATIONS PER SECTION C101.5.1. |
| | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE VENTILATION CALCULATIONS- SEE ASHRAE 62 |
| | INDOOR AIR QUALITY PROCEDURE AND TABLE 403.3 FBC-14 |
| | MECHANICAL. INDICATE ON THE PLAN THE REQUIRED CFM'S OF |
| | OUTSIDE AIR FOR ALL ROOMS AND SPACES, AND THE AMOUNT OF |
| | O/A CFM'S PROVIDED BY THE EXISTING AC SYSTEMS. PROVIDE |
| | DETAILS AND DRAWINGS FOR ALL REQUIRED UPGRADES IN THE |
| | EVENT THE EXISTING SYSTEMS ARE NOT CAPABLE OF |
| | SUPPORTING THE NEW OCCUPANCIES. PLEASE NOTE REFERENCE |
| | IS MADE TO DOCTOR'S OFFICES ON SHEET M2, HOWEVER THE |
| | PLANS DON'T INDICATE ANY DOCTOR'S OFFICES. |
| | 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC |
| | SYSTEMS ON THE PLAN, AND CLARIFY IF THEY ARE EQUIPPED |
| | WITH DUCT SMOKE DETECTORS. PROVIDE A SEQUENCE OF |
| | OPERATION FOR THE DEVICES IF APPLICABLE. |
| | 4) INDICATE ON THE PLAN HOW ACCESS TO THE AC AIR |
| | HANDLERS WILL BE PROVIDED FOR SERVICE, REPAIR, OR |
| | REPLACEMENT- SEE SECTION 306.1 FBC-14 MECHANICAL. |
| | 5) PROVIDE A DETAIL ON THE PLAN FOR INSTALLATION OF THE |
| | FIRE DAMPERS PER MANUFACTURER'S SPECIFICATIONS, AND |
| | SUBMIT CUT SHEETS REVIEWED AND APPROVED BY THE ENGINEER |
| | OF RECORD. INDICATE HOW THE DAMPERS WILL BE ACTUATED- |
| | SEE SECTION 607.3.3, AND CLARIFY IF THEY WILL BE LINKED |
| | TO A FIRE ALARM SYSTEM. |
| | 6) INDICATE ON THE PLANS HOW ACCESS TO THE FIRE DAMPERS |
| | FOR SERVICE AND MAINTRENANCE WILL BE PROVIDED, AND SHOW |
| | ACCESS DOOR LOCATIONS. |
| | 7) REFER TO SECTION 3006.2 FBC-14 BUILDING CODE AND |
| | PROVIDE INDEPENDENT VENTILATION SYSTEMS FOR THE IT |
| | ROOMS IF SOLID STATE EQUIPMENT FOR THE ELEVATORS IS |
| | BEING HOUSED IN THOSE ADJACENT ROOMS. |
| | 8) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE |
| | DOWN OF THE NEW AC O/A INTAKE VENTILATOR, AND THE |
| | TOILET ROOM EXHAUST VENTILATOR ON THE ROOF. SUBMIT CUT |
| | SHEETS, AND NOA'S OR FL. PRODUCT APPROVALS FOR THE |
| | VENTILATORS REVIEWED AND APPROVED BY THE ENGINEER OF |
| | RECORD. |
| | 9) PLEASE NOTE ADDITIONAL MECHANICAL COMMENTS MAY |
| | FOLLOW RESPONSES TO ALL BUILDING DEPARTMENT REVIEWS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |