| 2015-12-23 10:25:15 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | MIKE ALBARRAN |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | PLEASE FOLLOW UP ON BUILDING AND FIRE COMMENTS IN ORDER |
| | TO COMPLY WITH THE ELECTRICAL REVIEW. |
| | PROVIDE EXISTING INFORMATION OF RISER DIAGRAM AND LOAD |
| | CALCS , WIRE SIZES , INSULATION TYPE , CONDUIT SIZES , |
| | AND ETC. |
| | PROVIDE A NARRATIVE DETAILED SCOPE OF WORK. WPB FBC |
| | 107.2.1 |
| | AIC CALCULATIONS REQUIRED FOR 400 AMP DISCONNECT TO |
| | HOUSE PANELS. ( CURRENT LIMITING FUSES ? ) |
| | |
| | 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT CURRENT |
| | RATINGS, |
| | AND OTHER CHARACTERISTICS. THE OVERCURRENT PROTECTIVE |
| | DEVICES, THE TOTAL IMPEDANCE, THE EQUIPMENT |
| | SHORTCIRCUIT |
| | CURRENT RATINGS, AND OTHER CHARACTERISTICS OF THE |
| | CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND |
| | COORDINATED TO |
| | PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR A |
| | FAULT TO |
| | DO SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL |
| | EQUIPMENT |
| | OF THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE |
| | EITHER BETWEEN |
| | TWO OR MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY |
| | CIRCUIT CONDUCTOR AND THE EQUIPMENT GROUNDING |
| | CONDUCTOR( |
| | S) PERMITTED IN 250.118. LISTED EQUIPMENT APPLIED IN |
| | ACCORDANCE WITH THEIR LISTING SHALL BE CONSIDERED TO |
| | MEET THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | 110.15 HIGH-LEG MARKING. ON A 4-WIRE, DELTA-CONNECTED |
| | SYSTEM WHERE THE MIDPOINT OF ONE PHASE WINDING IS |
| | GROUNDED, ONLY THE CONDUCTOR OR BUSBAR HAVING THE |
| | HIGHER |
| | PHASE VOLTAGE TO GROUND SHALL BE DURABLY AND |
| | PERMANENTLY |
| | MARKED BY AN OUTER FINISH THAT IS ORANGE IN COLOR OR BY |
| | OTHER |
| | EFFECTIVE MEANS. SUCH IDENTIFICATION SHALL BE PLACED AT |
| | EACH |
| | POINT ON THE SYSTEM WHERE A CONNECTION IS MADE IF THE |
| | GROUNDED CONDUCTOR IS ALSO PRESENT. |
| | |
| | PLEASE PROVIDE ADEQUATE WIRE GUTTER SIZES ACCORDING TO |
| | NEC |
| | |
| | (A) DEFLECTED INSULATED CONDUCTORS. WHERE INSULATED |
| | CONDUCTORS |
| | ARE DEFLECTED WITHIN AN AUXILIARY GUTTER, EITHER AT THE |
| | ENDS OR WHERE CONDUITS, FITTINGS, OR OTHER RACEWAYS OR |
| | CABLES |
| | ENTER OR LEAVE THE GUTTER, OR WHERE THE DIRECTION OF |
| | THE GUTTER IS |
| | DEFLECTED GREATER THAN 30 DEGREES, DIMENSIONS |
| | CORRESPONDING |
| | TO ONE WIRE PER TERMINAL IN TABLE 312.6(A) SHALL APPLY. |
| | (B) AUXILIARY GUTTERS USED AS PULL BOXES. WHERE |
| | INSULATED |
| | CONDUCTORS 4 AWG OR LARGER ARE PULLED THROUGH AN |
| | AUXILIARY |
| | GUTTER, THE DISTANCE BETWEEN RACEWAY AND CABLE ENTRIES |
| | ENCLOSING THE SAME CONDUCTOR SHALL NOT BE LESS THAN |
| | THAT REQUIRED |
| | IN 314.28(A)(1) FOR STRAIGHT PULLS AND 314.28(A)(2) FOR |
| | ANGLE PULLS. |