| 2015-11-20 16:37:00 | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW DISTANCE FROM WATER HEATER .HOT WATER |
| | SYSTEM SHALL CONFORM TO FBC P SEC 607.2 HOT OR TEMPERED |
| | WATER SUPPLY TO FIXTURES. |
| | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| | (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER. |
| | 2.VENT NEEDED ON TH SIDE WHERE THER ARE 2 FLOOR SINKS |
| | AND1 FLOOR DRAIN.SHALL COMPLY WITH FBC P SEC 915.2.3 |
| | CONNECTION. |
| | THE COMBINATION WASTE AND VENT SYSTEM SHALL BE PROVIDED |
| | WITH A DRY VENT CONNECTED AT ANY POINT WITHIN THE |
| | SYSTEM OR THE SYSTEM SHALL CONNECT TO A HORIZONTAL |
| | DRAIN THAT IS VENTED IN ACCORDANCE WITH ONE OF THE |
| | VENTING METHODS SPECIFIED IN THIS CHAPTER. COMBINATION |
| | WASTE AND VENT SYSTEMS CONNECTING TO BUILDING DRAINS |
| | RECEIVING ONLY THE DISCHARGE FROM A STACK OR STACKS |
| | SHALL BE PROVIDED WITH A DRY VENT. THE VENT CONNECTION |
| | TO THE COMBINATION WASTE AND VENT PIPE SHALL EXTEND |
| | VERTICALLY TO A POINT NOT LESS THAN 6 INCHES (152 MM) |
| | ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE BEING |
| | VENTED BEFORE OFFSETTING HORIZONTALLY. |
| | 3.GRAB BARS SHALL BE MEASURED FROM THE TOP OF THE |
| | GRIPPING SURFACE. PER FBC ACC. SEC 609.4 |
| | 4. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC. |
| | SEC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |