| 2016-01-08 13:48:00 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110532 |
| | ADD: 2302 PRESIDENTIAL WAY |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-689-8880 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: FRIDAY JAN. 08/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SEMI-COMPLIED. SITE PLAN SUBMITTED. |
| | 1A) NEW COMMENT. THE SUBMITTED (2) SITE PLANS SHOW |
| | EITHER THE DELETION OR ADDITION OF PROPERTY LINES. |
| | THE SITE PLAN DATED 6/12/2012 SHOWS THE MODULAR |
| | BUILDING BEING SET WITHIN 5-0? OF THE PROPERTY LINE |
| | WHEREAS THE SITE PLAN DATED 8/15/2013 IT APPEARS THERE |
| | WAS EITHER A UNITY OF PROPERTY OR A REPLAT OF THIS |
| | AREA. PLEASE PROVIDE ADDITIONAL INFORMATION, IS THE |
| | INTERNAL ROAD TO THE SITE GOING TO HAVE ITS OWN NAME |
| | AND ADDRESS. BEFORE PERMIT ISSUANCE THE CITY WILL NEED |
| | TO ASSIGN ADDRESSES TO THE SITE. THE CITY CONTACT IS |
| | MIKE ORIO |
| | TEL: 561-494-1080 |
| | E-MAIL: [email protected] |
| | |
| | 1B) BOTH SITE PLANS LIST THE CLUBHOUSE STRUCTURE AS |
| | TEMPORARY, PLEASE PROVIDE THE DATES THIS STRUCTURE WILL |
| | BE OCCUPIED FOR USE. 108.1 GENERAL. THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR TEMPORARY |
| | STRUCTURES AND TEMPORARY USES. SUCH PERMITS SHALL BE |
| | LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT BE |
| | PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING OFFICIAL |
| | IS AUTHORIZED TO GRANT EXTENSIONS FOR DEMONSTRATED |
| | CAUSE. |
| | 105.1 TIME LIMITATION. THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO GRANT ONE OR MORE (2) EXTENSIONS OF TIME |
| | FOR ADDITIONAL PERIODS NOT EXCEEDING THREE MONTHS EACH. |
| | THE EXTENSION SHALL BE REQUESTED IN WRITING PRIOR TO |
| | THE ABANDONMENT DATE AND JUSTIFIABLE CAUSE |
| | DEMONSTRATED. |
| | |
| | 2) THE MOD SPACE PLANS DO NOT HAVE A DCA STATE APPROVAL |
| | . SUBMITTED ARE LETTERS CONFIRMING THAT MODSPACE-MIAMI |
| | HAS BEEN ACCEPTED INTO THE MODULAR PROGRAM AND ARE |
| | CURRENT. LOST PLANS CAN BE SUBMITTED ?AS BUILT? |
| | PREPARED, SIGNED & SEALED BY A ARCHITECT. |
| | |
| | 2A) THE ?AS BUILT? PLANS SHOW A OCCUPANCY OF A BUSINESS |
| | OCCUPANCY. PLEASE NOTE THE (2) SITE PLANS INDICATE THE |
| | USE OF THIS STRUCTURE IS LABELED AS A CLUBHOUSE, FOR |
| | THE SQUARE FEET OF THE BUILDING AND PROPOSED OCCUPANT |
| | LOAD OF AN A3 ASSEMBLY BUILDING THE MODULAR PLANS WOULD |
| | NEED TO BE RE-DESIGNED FOR OCCUPANT LOAD, FLOOR |
| | LOADING, ACCESSIBLE EGRESS PATH, ENERGY CALCULATIONS, |
| | PLUMBING AND MECHANICAL SYSTEMS. DISCREPANCY IN PLANS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2B) PLEASE PROVIDE A WRITTEN DOCUMENT WHO THE ARCHITECT |
| | OF RECORD WILL BE SINCE THE SUBMITTED SET OF PLANS HAS |
| | (3) DIFFERENT ARCHITECTURAL SHEETS WITHIN THE SET OF |
| | PLANS, AND WHO WILL BE TAKING RESPONSIBILITY OF |
| | COORDINATING THE PLANS AND NARRATIVE RESPONSES. |
| | 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER |
| | ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS? |
| | OFFICE. |
| | |
| | 2C) PLEASE SEE THE RANDALL STOFFTS SHEETS A001 & A101 |
| | INDICATE THE PROPOSED CLUBHOUSE AS AN EXISTING |
| | STRUCTURE PLEASE CORRECT, UNDER THIS PERMIT BOTH THE |
| | PROPOSED WORK, CLUBHOUSE, LANDING, RAMP, STAIR HAND |
| | RAIL & GUARD RAIL WILL BE UNDER THIS PERMIT. |
| | |
| | 2D) THE PLANS DESIGNED UNDER MODSPACE WILL NEED |
| | RE-EVALUATING IF THE A-3 ASSEMBLY (CLUBHOUSE/ COMMUNITY |
| | HALL) SINCE THE FLOOR LOADS WOULD NEED TO COMPLY WITH |
| | 2014 FBC-B TABLE 1607.1(4) ASSEMBLY AREAS FOOTNOTE M. |
| | |
| | 2E) DISCREPANCY IN PLANS. MODSPACE PLANS SHOWS 3 SETS |
| | OF DOORS WHEREAS RANDELL STOFFT PLANS ONLY SHOW 2 |
| | DOORWAYS. DISCREPANCY IN PLANS. |
| | |
| | 2F) IF THIS PROJECT IS TO BE CONSIDERED AN A3 OCCUPANCY |
| | AND THE OCCUPANT LOAD WOULD BE GREATER THAN 50 THERE |
| | WILL BE THE NEED FOR 2 ACCESSIBLE EXITS ? THE OVERALL |
| | DIAGONAL DISTANCE APART (NON-SPRINKLERED). |
| | PLEASE SEE 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE |
| | MEANS OF EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION |
| | 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF |
| | EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT |
| | LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. |
| | |
| | 2G) MODSPACE COVERSHEET UNDER THE HEADING OF STRUCTURAL |
| | LOAD LIMITATION/ WIND DESIGN CRITERIA HAS THE VASD & |
| | VULT REVERSED. 146VULT/ 188 VASD MPH 107.2.1.3 |
| | DISCREPANCY IN PLANS, CORRECT. |
| | |
| | |
| | 3-5) COMPLIED. STORM SHUTTERS PERMIT # 15120406. |
| | |
| | 6) DESIGN DOCUMENTS BY RANDELL STOIFT ARCHITECT FOR |
| | ACCESSIBLE STAIRS, RAMP AND LANDING: |
| | |
| | 6A) COMPLIED |
| | |
| | 6B) COMPLIED. |
| | |
| | 6C) SEMI-COMPLIED. SHEET A101.THE MID-LANDING SET AT A |
| | HEIGHT OF 15.5 INCHES DOES NOT SHOW COMPLIANCE WITH |
| | 2014 FBC-ACCESSIBILITY CODE 405.8 HANDRAILS. RAMP RUNS |
| | WITH A RISE GREATER THAN 6 INCHES (150 MM) SHALL HAVE |
| | HANDRAILS COMPLYING WITH 505. |
| | |
| | 505.3 CONTINUITY. |
| | HANDRAILS SHALL BE CONTINUOUS WITHIN THE FULL LENGTH OF |
| | EACH STAIR FLIGHT OR RAMP RUN. INSIDE HANDRAILS ON |
| | SWITCHBACK OR DOGLEG STAIRS AND RAMPS SHALL BE |
| | CONTINUOUS BETWEEN FLIGHTS OR RUNS. |
| | |
| | 405.9 EDGE PROTECTION. EDGE PROTECTION COMPLYING WITH |
| | 405.9.1 OR 405.9.2 SHALL BE PROVIDED ON EACH SIDE OF |
| | RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |