| Date |
Text |
| 2015-12-02 09:41:44 | 2302 PRESIDENTIAL WAY - CONSTRUCTION TRAILERS |
| | PERMIT #15110532 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | STATUS ? FAILED BY FIRE DEPARTMENT. SUBMIT REVISION |
| | ADDRESSING PLAN REVIEW COMMENTS: |
| | |
| | **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE |
| | OCCUPANCY OF THE STRUCTURE IS PERMITTED** |
| | |
| | PROVIDE A PLAN SHOWING THE CONFIGURATIONS AND LOCATIONS |
| | OF THE TRAILERS IN CORRELATION TO OTHER STRUCTURES. |
| | SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. PLEASE IDENTIFY AND SHOW |
| | CLOSET FIRE HYDRANT TO THE PROPOSED TRAILER. |
| | |
| | NO PLAN DETAILS SUBMITTED FOR STAIRS, HANDRAILS OR |
| | GUARDRAILS. HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE |
| | STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 |
| | INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF |
| | THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE RAIL |
| | FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL |
| | BE RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| | 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE |
| | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, |
| | MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. |
| | OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH |
| | DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE |
| | TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND |
| | BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE |
| | PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL |
| | BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS |
| | SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH |
| | OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER. NO |
| | PLATFORM / RAMP DETAILS ARE SHOWN FOR REAR EXIT / ENTRY |
| | DOUBLE DOORS. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | NOTE: PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; |
| | TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE |
| | REQUIRED IN EACH TRAILER. ALL TRAILERS GREATER THAN A |
| | ?DOUBLE WIDE? IN THE CITY OF WEST PALM BEACH IS |
| | REQUIRED TO BE SPRINKLED. PLEASE PROVIDE PLANS FOR A |
| | MONITORED SPRINKLER AS A SEPARATE/SUB PERMIT. |
| | |
| | |