| 2015-12-04 12:37:54 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE |
| | LOCATION OF THE VARIOUS COMPONENTS OF THIS |
| | INSTALLATION. |
| | A) INDICATE ON PLAN THE PROPOSED ROUTE OF ALL FEEDERS; |
| | WHETHER AERIAL OR UNDERGROUND. (ALL TRENCHING SHALL |
| | REMAIN OPEN FOR INSPECTION. NO SITE TUBES WILL BE |
| | ALLOWED) |
| | B) INDICATE THE DISTANCE FOR EACH FEEDER FOR VOLTAGE |
| | DROP CALCULATIONS. |
| | 2. NEC 215.5 YOU SHALL PROVIDE A FEEDER DIAGRAM |
| | INDICATING IN ADDITION TO THE ABOVE, THE LOAD CALCS AND |
| | CONDUCTOR SIZING AND INSULATION. |
| | 3. NEC 408.4 PROVIDE A CIRCUIT DIRECTORY AND MARK EVERY |
| | PANELBOARD WITH THE LOCATION OF THE SOURCE DISCONNECT. |
| | 4. NEC 110.16 ALL EQUIPMENT SHALL BE MARKED WITH THE |
| | ARC-FLASH WARNING HAZARD LABEL. |
| | 5. IN ADDITION TO THE ELECTRICAL SERVICE FOR THESE |
| | UNITS, FBC SECTION 1006 REQUIRES THAT THE MEANS OF |
| | EGRESS BY PROPERLY ILLUMINATED DURING THE TIME OF |
| | OCCUPANCY. THE DRAWINGS DO NOT REFLECT ADEQUATE |
| | ILLUMINATION. |
| | 6. FBC FURTHER REQUIRES THAT THESE AREAS BE PROVIDED |
| | WITH EMERGENCY LIGHTING. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |