| 2015-11-25 14:48:02 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110532 |
| | ADD: 2302 PRESIDENTIAL WAY |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-689-8880 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 25/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE SUBMIT A SITE PLANS MISSING FROM THE 1ST |
| | REVIEW. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | FOR BUILDINGS. 107.3.5.1.1 COMMERCIAL BUILDINGS (1.) |
| | SITE PLAN REQUIREMENTS: |
| | LOCATION OF JOBSITE. |
| | PARKING |
| | FIRE ACCESS |
| | VEHICLE LOADING |
| | DRIVING/TURNING RADIUS |
| | FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| | SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| | LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| | FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| | ELEVATIONS |
| | |
| | 2) THE MOD SPACE PLANS DO NOT HAVE A DCA STATE APPROVAL |
| | BY A 3RD PARTY AGENCY. THE PLANS ARE THE EQUIVALENT TO |
| | A SITE BUILT STRUCTURE. CAN INSPECTION AFFADAVITS FROM |
| | THE MANUFACTURER PLANT BE OBTAINED, IF NOT THE |
| | STRUCTURE HAS TO BE OPENED UP FOR THE CITY STAFF TO BE |
| | ABLE TO VERIFY CODE COMPLIANCE. |
| | |
| | 3) THIS STRUCTURE IS GOING TO BE USED AS TEMPORARY GOLF |
| | FACILITY. THE TERM TEMPORARY IS LESS THAN 180 DAYS. THE |
| | USE WILL REQUIRE COMPLIANCE WITH EITHER LARGE MISSILE |
| | IMPACT WINDOWS OR STORM SHUTTERS FOR ALL GLAZED |
| | OPENINGS. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (E) SHUTTERS |
| | |
| | 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) STORM SHUTTERS. PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC |
| | ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT |
| | GLAZING. FBC 1609.1.2. |
| | FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A |
| | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & |
| | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR. |
| | |
| | 6) DESIGN DOCUMENTS BY RANDELL STOIFT ARCHITECT FOR |
| | ACCESSIBLE STAIRS, RAMP AND LANDING: |
| | |
| | 6A) SHEET A001 DESIGN PARAMETERS INDICATE BUILDING |
| | CLASSIFICATION AS A R-3 OCCUPANCY, BUT THE PLANS STATE |
| | TEMPORARY GOFL FACILITY. PLEASE CORRECT OCCUPANCY |
| | PROUP. 2010 FBC-B 304.1. |
| | |
| | 6B) NO WIND DESIGN WAS PROVIDED ON ANY OF THE PLANS. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 6C) SHEET A101 & A102 ARE DETAIL SHEETS THA ARE |
| | INCOMPLETE. THERE ARE MANY IDENTIFICATION TAGS, BUT NO |
| | LEGEND AS TO WHAT THEY ARE. THERE ARE NO HEIGHT |
| | DIMENSIONS FOR HANDRAILS NOR GUARDRAILS. THE PLANS ARE |
| | BASICALLY INCOMPLETE IN FOR THE SCOPE OF WORK OUTLINED. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | |
| | 6D) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |