2015-11-29 07:46:481) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. WPB AMEND. TO SEC.107.2.1.
 2) THE WATER SHUTOFF VALVES FOR THE WASHING MACHINE
 SHALL NOT BE LOCATED BEHIND THE W/D STACK MODEL UNLESS
 THERE IS AN ACCESS PANEL ON THE W/D UNIT FOR THE
 VALVES. SUBMIT MANUF.SPECIFICATIONS FOR THE
 WASHER/DRYER UNIT.2014 FBC-RESIDENTIAL SEC. P2903.9.3.
 3) SHT. B-P-1 - NOTES- NOTE #3 STATES THAT THE HOT
 WATER HEATER TO BE SIZED PER TABLE 46-N-8.WHAT
 STANDARD/CODE IS THIS TABLE FROM? I COULDN'T FIND IT
 IMY CODE BOOKS. CLARIFY.
 4) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.3 (11).
 5) THE PLUMBING PLANS REFER TO SHEET SP-1 FOR
 CONTINUATION OF THE WATER SERVICE. SHT. SP-1 IS NOT
 PART OF THIS SET. SUBMIT SHT. SP-1 FOR REVIEW.
  