| Plan Review Notes For Permit 15110510 |
| Permit Number |
15110510 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-26 16:26:48 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15110510 | | | 2/26/16 | | | | | | 1) THE RESPONSE NARRATIVE FROM INTERPLAN INDICATES | | | REVISED AC CALCULATIONS HAVE BEEN SUBMITTED, HOWEVER | | | THERE ARE NO REVISED CALCS SUBMITTED FOR REVIEW- SEE | | | COMMENT #1 FROM THE 1ST REVIEW. | | | 2) THE ENERGY CALCULATIONS ARE INDICATING 13 SEER FOR | | | THE RTU-1 & 2, HOWEVER THE EFFICIENCY RATINGS FOR THESE | | | SYSTEMS ARE NOT SHOWN ON THE SCHEDULE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|