Plan Review Notes
Plan Review Notes For Permit 15110510
Permit Number 15110510
Review Stop M
Sequence Number 1
Notes
Date Text
2015-11-18 17:44:381ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110510
 11/18/15
  
 1) THE SUBMITTED AC COOLING AND HEATING CALCULATIONS
 SHOW A TOTAL LOAD OF 137.2 MBH FOR RTU'S 1, 2, &3,
 HOWEVER THE AC SCHEDULE ON SHEET M5.0 INDICATES A
 COMBINED TOTAL COOLING LOAD OF 307.1 MBH: SEE SECTION
 C403.2.2 FBC-14 ENERGY CONSERVATION- OUTPUT CAPACITY
 CANNOT EXCEED THE CALCULATED LOAD.
 2) THE AC SCHEDULE INDICATES AN EFFICIENCY RATING OF 11
 EER FOR RTU-2: SEE TABLE C403.2.3(1)- MINIMUM
 EFFICIENCY RATING FOR UNITS <65,000 BTUH IS 13 SEER.
 3) THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014
 INDICATES AN 11 EER FOR OAU-1, HOWEVER NO RATING IS
 GIVEN IN THE AC SCHEDULE ON M5.0.
 4) THE OUTSIDE AIR CALCULATION SCHEDULE ON SHEET M5.0
 INDICATES 3008 CFM'S REQUIRED FOR THE DINING AND DELI
 AREAS, HOWEVER THE AIR BALANCE DIAGRAM ON M4.2
 INDICATES ONLY 2100 CFM BEING PROVIDED BY OAU-1, AND 0
 CFM PROVIDED BY THE RTU'S IN THOSE AREAS: PLEASE
 CLARIFY OR CORRECT. ADDITIONALLY, PLEASE NOTE THE
 DEFICIENCY IN OUTSIDE AIR FOR OCCUPANTS IN THE KITCHEN
 AND AT THE COOKLINE. ALL AIR BEING SUPPLIED TO THE
 KITCHEN IN THE DIAGRAM IS FOR EXHAUST MAKE-UP AIR- SEE
 SECTION 403.2 FBC-14 MECHANICAL.
 5) PLEASE COMPLETE THE COMPLIANCE CHECKLIST ON ENERGY
 FORM 506-2014.
 6) REFER TO SECTION 304 FBC-14 FUEL GAS AND INDICATE
 WHAT METHOD WILL BE UISED TO PROVIDE COMBUSTION AIR TO
 THE GAS-FIRED COOKING APPLIANCES IN THE KITCHEN, AND
 INCLUDE A CALCULATION- PLEASE TAKE NOTE OF SECTION
 304.9.3 COMBIMNED COMBUSTION AND VENTILATION AIR.
 7) SHEET A8.0: INDICATE HOW ACCESS TO THE EQUIPMENT ON
 THE ROOF IS BEING PROVIDED- REFER TO SECTION 306.5
 FBC-14 MECHANICAL.
 8) M4.2: REFER TO SECTION 301.15 AND PROVIDE THE WIND
 LOAD DESIGN CRITERIA FOR TIE DOWN OF THE ROOF TOP
 EQUIPMENT INCLUDING RTU'S AND FANS: WIND DESIGN
 CRITERIA 2014 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.1609.3
 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 A) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 B) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 9) M4.0: PROVIDE ENGINEERED TIE DOWN DETAILS FOR ALL OF
 THE ROOFTOP FANS SHOWN- DETAILS 8, 11, & 12.
 10) PLEASE NOTE THAT THE CITY OF WPB CONSTRUCTION
 SERVICES DEPT. REQUIRES SEPARATE PERMIT APPLICATIONS,
 PLANS, AND SUBMITTALS FOR THE KITCHEN HOODS AND FIRE
 SUPRESSION SYSTEMS, AND FOR WALK-IN BOXES AND
 REFRIGERATION SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719