 GAS COMMENTS:
  
 1.SHT. P6.0 GAS RISER KITCHEN EQUIPMENT SCHEDULE #8 IS
 CALLING OUT 240 CFM BTU LOAD SIZED AT 60FT USING THE
 LONGEST LENGTH METHOD THAT BRANCH SHOULD BE 11/4IN .TO
 COMPLY WITH FBC FUEL GAS TABLE 402.4(1) AND SEC 402.4.1
  
 2.SHT. P6.0 GAS RISER KITCHEN EQUIPMENT SCHEDULE #2+4
 IS CALLING OUT 110+108 CFM BTU LOAD SIZED AT 60FT USING
 THE LONGEST LENGTH METHOD THAT BRANCH SHOULD BE 1IN .TO
 COMPLY WITH FBC FUEL GAS TABLE 402.4(1) AND SEC
 402.4.1.
  
 3.SHT.P6.0 IT APPEARS THAT ON RISER DIAGRAM YOUR BTU
 LOAD AND KITCHEN EQUIPMENT SCHEDULE # IS REVERSED FOR
 8+9 THEY DON'T MATCH THE SCHEDULE ON SHT. K1.5 PLEASE
 CLARIFY. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 4. COMBUSTION AIR CALCULATIONS NOTE 2. THE MAKE UP AIR
 FOR THAT HOOD IS CALCULATED FOR THE HOOD ONLY IF YOU
 ARE USING MECHANICAL COMBUSTION AIR IT SHALL COMPLY
 WITH FBC FUEL GAS SEC.304.9.3 COMBINED COMBUSTION AIR
 AND VENTILATION AIR SYSTEM.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING?S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. PLEASE CLARIFY