| Date |
Text |
| 2016-01-26 14:55:08 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. ADDITIONAL EMERGENCY ILLUMINATION SHALL BE PROVIDED |
| | FOR THE AREA OUTSIDE OF HALLWAY 103 AS WELL AS THE AREA |
| | ADJACENT TO THE DRY STORAGE. |
| | 2. THE SIGN OUTLET PROVIDED DOES NOT COMPLY WITH THE |
| | REQUIREMENTS OF NEC 600.5 WHICH REQUIRES THAT EACH |
| | COMMERCIAL BUILDING AND EACH COMMERCIAL OCCUPANCY |
| | ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT |
| | LEAST ONE 20 AMP DEDICATED OUTLET IN AN ACCESSIBLE |
| | LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| | OR OUTLINE LIGHTING. SERVICE HALLWAYS OR CORRIDORS |
| | SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| | 3. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 4. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| | PADDLE FANS HEAVIER THAN 70 LBS. |
| | 5. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY. |
| | 6. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 |
| | VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR |
| | THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL |
| | BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. |
| | 7. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. |
| | 8. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | 9. THE NEW 120/208 3? SERVICE BY LANDLORD REQUIRES A |
| | PERMIT OF ITS OWN. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| | NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |