Plan Review Notes
Plan Review Notes For Permit 15110510
Permit Number 15110510
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-26 14:55:08THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. ADDITIONAL EMERGENCY ILLUMINATION SHALL BE PROVIDED
 FOR THE AREA OUTSIDE OF HALLWAY 103 AS WELL AS THE AREA
 ADJACENT TO THE DRY STORAGE.
 2. THE SIGN OUTLET PROVIDED DOES NOT COMPLY WITH THE
 REQUIREMENTS OF NEC 600.5 WHICH REQUIRES THAT EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE 20 AMP DEDICATED OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 3. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 4. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 5. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 6. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125
 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
 7. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 8. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 9. THE NEW 120/208 3? SERVICE BY LANDLORD REQUIRES A
 PERMIT OF ITS OWN.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746