| Plan Review Notes For Permit 15110501 |
| Permit Number |
15110501 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-25 14:45:56 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. | | | FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE | | | COMPLIANCE CERTIFICATION. | | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. (THE EQUIPMENT SPECIFIED ON THE MECHANICAL | | | PLANS ARE REQUIRED TO MATCH THE ENERGY FORMS AND | | | CALCULATIONS). | | | | | | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | |
|