| 2015-12-11 17:43:27 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ELECTRICAL PLANS REFERENCE THE 2008 NEC. THE |
| | 2011 NEC IS THE EDITION OF NEC THAT IS CURRENTLY |
| | REFERENCED BY THE 2014 FBC. |
| | |
| | 2) THE ELECTRICAL PROVISIONS OF THE 2014 |
| | FBC-RESIDENTIAL WILL APPLY TO THIS PROJECT. |
| | |
| | 3) SHOW COMPLIANCE WITH FBCR-E3901.12 FOR REQUIRED HVAC |
| | SERVICE OUTLET RECEPTACLES. |
| | |
| | 4) SHOW COMPLIANCE WITH FBCR-E3901.7 FOR REQUIRED |
| | RECEPTACLE OUTLETS AT FRONT AND REAR OF DWELLING. |
| | |
| | 5) FBCR-E 3901.2.1 OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET. |
| | |
| | 6) NOTE S ON SHEET E3 STATES THAT BEDROOM OUTLETS ARE |
| | TO BE AFCI PROTECTED. THE CURRENT ELECTRICAL CODE |
| | REQUIRES AFCI PROTECTION FOR RECEPTACLE OUTLETS LOCATED |
| | IN OTHER ROOMS AS WELL. SEE FBCR-E3902.12 FOR LIST OF |
| | ROOMS THAT REQUIRE AFCI PROTECTION. |
| | |
| | 7) GARAGE AND OUTDOOR RECEPTACLES ARE REQUIRED TO BE |
| | GFCI PROTECTED. FBCR-E 3902 |
| | |
| | 8) SHOW COMPLIANCE WITH FBCR-E3609.3 FOR REQUIRED |
| | INTERSYSTEM BONDING TERMINATION. |
| | |
| | 9) THE ELECTRICAL RISER DIAGRAM ON SHEET E3 HAS |
| | TRANSFER SWITCH ON PANEL B. IS THERE GOING TO BE A |
| | FUTURE GENERATOR WITH A TRANSFER SWITCH (SEPARATE |
| | PERMIT REQUIRED) INSTALLED TO FEED THIS PANEL FOR |
| | EMERGENCY POWER. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | |