| 2015-12-11 09:09:53 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE DRAWING INDEX ON SHEET T1 DOES NOT MATCH THE |
| | DRAWINGS THAT WERE SUBMITTED. SHEETS T2, A1.3A, A4 AND |
| | P3 ARE MISSING. |
| | |
| | 2) SHEETS T1, D1 AND D2 REFERENCE THE 2008 NEC AND THE |
| | 2011 NEC IS THE CURRENT EDITION. |
| | |
| | 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION |
| | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER |
| | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS |
| | 402 OR 405. |
| | FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE |
| | COMPLIANCE CERTIFICATION. |
| | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | |
| | 4) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS |
| | PROJECT HAS A V ULTIMATE WIND SPEED OF 170 MPH AND THE |
| | EXPOSURE CATEGORY IS D. FBC-R301.2.1 |
| | |
| | 5) SHOW COMPLIANCE WITH FBC-R317.1 PROTECTION OF WOOD |
| | AND WOOD BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN |
| | THE FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE |
| | WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE |
| | WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND |
| | END USE. PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF |
| | AWPA U1. |
| | 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR |
| | WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS |
| | WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED |
| | GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED |
| | WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION. |
| | |
| | 6) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL |
| | HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM |
| | AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS |
| | HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) |
| | SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH |
| | SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH |
| | OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) |
| | MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF |
| | FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF |
| | SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL |
| | OPEN DIRECTLY TO THE OUTSIDE AIR. |
| | |
| | 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 8) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR |
| | NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND |
| | MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS. (BUR AND CONCRETE BARREL TILE) |
| | |
| | |
| | |
| | |
| | |
| | |