Plan Review Notes
Plan Review Notes For Permit 15110501
Permit Number 15110501
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-11 09:09:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DRAWING INDEX ON SHEET T1 DOES NOT MATCH THE
 DRAWINGS THAT WERE SUBMITTED. SHEETS T2, A1.3A, A4 AND
 P3 ARE MISSING.
  
 2) SHEETS T1, D1 AND D2 REFERENCE THE 2008 NEC AND THE
 2011 NEC IS THE CURRENT EDITION.
  
 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
 FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 4) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS
 PROJECT HAS A V ULTIMATE WIND SPEED OF 170 MPH AND THE
 EXPOSURE CATEGORY IS D. FBC-R301.2.1
  
 5) SHOW COMPLIANCE WITH FBC-R317.1 PROTECTION OF WOOD
 AND WOOD BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN
 THE FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE
 WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE
 WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND
 END USE. PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF
 AWPA U1.
 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR
 WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS
 WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED
 GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED
 WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION.
  
 6) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR.
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 8) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR
 NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS. (BUR AND CONCRETE BARREL TILE)
  
  
  
  
  
  