| 2015-11-17 07:44:42 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15110492 |
| | 11/17/15 |
| | |
| | 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | SPRAY BOOTH AND SPRAY EQUIPMENT REVIEWED AND STAMPED BY |
| | THE ENGINEER OF RECORD- REFERENCE NFPA 33 SECTIONS |
| | (5.1.1), )5.1.4), (7.10.1), (8.3.2), (11.1), (12.1). |
| | 2) THE LOCATIONS OF THE SPRAY BOOTH SHOWN ABUTTING THE |
| | EXTERIOR CONCRETE WALL AT THE EAST SIDE DOES NOT LEAVE |
| | AMPLE SPACE FOR MAINTENANCE AS REQUIRED BY SECTION |
| | 5.3.2 EXCEPTION (2) NFPA 33. |
| | 3) A 4X4' LOUVER IS SHOWN IN THE PLAN FOR MAKE-UP AIR. |
| | PLEASE PROVIDE AN EXHAUST VENTILATION CALCULATION USING |
| | THE PERCENTAGE OF FREE AIR AVAILABLE THROUGH THE |
| | LOUVERED OPENING- SECTION 502.7.3.1 FBC-14 MECHANICAL. |
| | 4) PROVIDE AN AIR VELOCITY CALCULATION FOR THE SPRAY |
| | BOOTH IN COMPLIANCE WITH SECTION 502.7.3.3 FBC-14 |
| | MECHANICAL. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL. |
| | PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVER |
| | REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. THE |
| | LOCATION OF THE LOUVERED OPENING SHALL BE IN COMPLIANCE |
| | WITH SECTION 401.4, AND BE PROTECTED FROM WEATHER IN |
| | ACCORDANCE WITH SECTION 401.5. |
| | 6) INDICATE HOW THE EXHAUST DUCT IS BEING SUPPORTED IN |
| | THE AREA BETWEEN THE TOP OF THE BOOTH AND THE ROOF |
| | LEVEL- SECTION 7.8 NFPA 33. |
| | 7) REFERENCE SECTION 501.3.1(1) FBC-14 MECHANICAL AND |
| | PROVIDE A PLAN VIEW OF THE ROOF AND SITE THAT SHOWS THE |
| | REQUIRED MINIMUM CLEARANCE DISTANCES FOR THE SPRAY |
| | BOOTH EXHAUST TERMINATION TO PROPERTY LINES, AIR |
| | INTAKES, COMBUSTIBLE CONSTRUCTION, EXTERIOR WALLS, AND |
| | OPERABLE OPENINGS. |
| | 8) INDICATE THE TYPE AND SIZE OF COMPRESSED AIR PIPING |
| | TO BE INSTALLED AND HOW IT WILL BE SUPPORTED- INDICATE |
| | THE TYPE AND SPACING OF THE HANGERS. |
| | 9) PROVIDE A THROUGH PENETRATION FIRE STOPPING METHOD |
| | FOR THE COMPRESSED AIR PIPING PENETRATING THE BOOTH. |
| | 10) PROVIDE FIRE SUPPRESSION PLANS- SECTION 9.1 NFPA |
| | 33. |
| | |