| Plan Review Notes For Permit 15110492 |
| Permit Number |
15110492 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-07 11:05:52 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | PHIL PETTY | | | 561-805-6742 | | | [email protected] | | | | | | | | | 430.6 AMPACITY AND MOTOR RATING DETERMINATION. THE | | | SIZE OF CONDUCTORS SUPPLYING EQUIPMENT COVERED BY | | | ARTICLE | | | 430 SHALL BE SELECTED FROM THE ALLOWABLE AMPACITY | | | TABLES IN | | | ACCORDANCE WITH 310.15(B) OR SHALL BE CALCULATED IN | | | ACCORDANCE | | | WITH 310.15(C). | | | (1) TABLE VALUES. OTHER THAN FOR MOTORS BUILT FOR LOW | | | SPEEDS | | | (LESS THAN 1200 RPM) OR HIGH TORQUES, AND FOR | | | MULTISPEED | | | MOTORS, THE VALUES GIVEN IN TABLE 430.247, TABLE | | | 430.248, | | | TABLE 430.249, AND TABLE 430.250 SHALL BE USED TO | | | DETERMINE | | | THE AMPACITY OF CONDUCTORS OR AMPERE RATINGS OF | | | SWITCHES, | | | BRANCH-CIRCUIT SHORT-CIRCUIT AND GROUND-FAULT | | | PROTECTION, INSTEAD | | | OF THE ACTUAL CURRENT RATING MARKED ON THE MOTOR | | | NAMEPLATE. WHERE A MOTOR IS MARKED IN AMPERES, BUT NOT | | | HORSEPOWER, THE HORSEPOWER RATING SHALL BE ASSUMED TO | | | BE | | | THAT CORRESPONDING TO THE VALUE GIVEN IN TABLE 430.247, | | | TABLE 430.248, TABLE 430.249, AND TABLE 430.250, | | | | | | PLEASE PROVIDE EQUIPMENT SPECS AND VERIFY LOCATION OF | | | EQUIPMENT AS IN OTHER COMMENTS | | | PLEASE PROVIDE A MORE DETAILED FIRE SYSTEM PLAN | | | | | | | | | | | | |
|