| Plan Review Notes For Permit 15110464 |
| Permit Number |
15110464 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-13 06:17:55 | 1) PER TABLE 402.4 (26) OF THE 2010 FBC-FUEL GAS AS | | | REFERENCED ON THE PLANS, THE MAXIMUM BTU LOAD ON A | | | 3/4"SCCHEDULE 40 METALLLIC PIPE LINE AT A TOTAL | | | DEVELOPED LENGTH OF 170 FT. FROM THE REGULATOR TO THE | | | FURTHEST OUTLET IS 155,000 BTU'S. THE PLAN SHOWS | | | 180,000 BTU'S ON A 3/4" LINE.THIS LLINE TO THE 2 RANGES | | | IS UNDERSIZED AND THE PIPE SIZE SHALL BE INCREASED TO A | | | MINIMUM OF ONE INCH PER THE GAS SIZING TABLE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|