2015-11-13 06:17:551) PER TABLE 402.4 (26) OF THE 2010 FBC-FUEL GAS AS
 REFERENCED ON THE PLANS, THE MAXIMUM BTU LOAD ON A
 3/4"SCCHEDULE 40 METALLLIC PIPE LINE AT A TOTAL
 DEVELOPED LENGTH OF 170 FT. FROM THE REGULATOR TO THE
 FURTHEST OUTLET IS 155,000 BTU'S. THE PLAN SHOWS
 180,000 BTU'S ON A 3/4" LINE.THIS LLINE TO THE 2 RANGES
 IS UNDERSIZED AND THE PIPE SIZE SHALL BE INCREASED TO A
 MINIMUM OF ONE INCH PER THE GAS SIZING TABLE.
  