2016-03-18 15:22:253RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110411
 3/18/16
  
 1) THE REVISED PLANS DO NOT PROVIDE A STRUCTURAL DETAIL
 FOR MOUNTING THE COLD ZONE UNIT TO THE ENGINEERED CURB-
 PLEASE PROVIDE THE ENGINEERING.
 2) SHEET S3: IT APPEARS THAT WORKING CLEARANCE ON THE
 NORTH SIDE OF THE COLD ZONE WILL BE OBSTRUCTED BY THE
 SKYLIGHT. IS THIS THE ACTUAL LOCATION OF THE UNIT?
  