| Plan Review Notes For Permit 15110411 |
| Permit Number |
15110411 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-01-04 11:10:49 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15110411 | | | 01/04/16 | | | | | | THE PREVIOUS (1ST) REVIEW COMMENTS STILL EXIST. I HAVE | | | REPRINTED THEM BELOW WITH SOME ADDITIONAL NOTES IN | | | PARENTHESIS. | | | 1) SUBMIT A REVISED M1.3 PLAN SHEET SHOWING THE | | | LOCATION OF THE COLDZONE MINI-PAK ROOFTOP UNIT. (THE | | | REQUESTED M1.3 SHEET WAS NOT REVISED AND SUBMITTED). | | | 2) SUBMIT A REVISED S3 SHEET SHOWING THE ROOFTOP | | | LOCATIONS OF THE COLDZONE MINI-PAK UNIT, AND THE | | | WALK-IN COOLER AND FREEZER CONDENSERS. (COLD ZONE | | | ROOFTOP UNIT IS NOT SHOWN ON THE REVISED S3 PLAN DATED | | | 12/18/15.) | | | 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE | | | MINI-PAK AND THE CONDENSERS TO THE ROOF STRUCTURE- | | | SECTION 301.12 FBC-10 MECHANICAL. PLEASE NOTE THAT THE | | | COLDZONE SUBMITTAL DOES NOT PROVIDE WIND LOAD DESIGN | | | CRITERIA OR STRUCTURAL DETAILS. (THERE ARE NOTES ON S3 | | | BY THE WALK-IN CONDENSERS REFERENCING THE ARCHITECTURAL | | | ROOF PLAN AND NOA'S, HOWEVER NEITHER WERE SUBMITTED). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|