Plan Review Notes
Plan Review Notes For Permit 15110411
Permit Number 15110411
Review Stop B
Sequence Number 2
Notes
Date Text
2016-01-15 11:40:31BUILDING PLAN REVIEW
 W. P. B. REVISION: 15110411
 W. P. B. PERMIT; 14120130
 ADD: 1901 S. DIXIE HWY
 CONT: SISCA CONSTRUCTION
 TEL: 561-846-1179
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: SAT. NOV. 14/2014
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) 2ND REQUEST. SHEET R-2 SHOWS THE USE OF A MINI-PAKT
 CONDENSING UNIT FOR ROOF TOP USE. IN DETAIL C/R-2
 SECTION A-A THE DETAIL SHOWS THE USE OF A 2X6 BUILT UP
 CURB. THIS DETAIL IS NOT FOR A RTU DOWN UNIT WHERE
 THERE WOULDBE NO ROOFING MATERIAL BENEATH IT. IT WOULD
 APPEAR 2 SLEEPERS OR CURBS WOULD BE REQUIRED PLACED IN
 PARALLELL WHERE WOULD BE ROOFING BENEATH IT.
  
 2ND REQUEST. PLEASE REVIEW SECTION 1509.7 OF THE 2010
 FBC-B. 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
 TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS
  
 2ND REQUEST. OF THE PERMITED SET OF DRAWINGS SHEET A4.0
 ONLY SHOWS THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH
 S3 & M1.3 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE
 3 RTU'S AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS
 A NOTE THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL
 LOCATIN SHALL BE DETERMINED BY OWNER/ ARCHITECT.
 REVISION # 15090594 DOES NOT SHOW A REVISION TO THE
 ROOF PLAN NOR WAS SHEET S3 UPDATED TO SHOW NEW
 LOCATIONS, SHEET M1.3 DOES SHOW ON THE MECHANICAL ROOF
 TOP SHEET A REVISION SHOWING THE LOCATION FOR 3 NEWLY
 LOCATED, (NOT HIGHLIGHTED SHOWING A REVISION), ROOF TOP
 CU UNITS, NO DETAILS UNDER MECHANICAL NOR STRUCTURAL
 SHEETS!!!!!
  
 2ND REQUEST. THE STRUCTURAL ENGINEER HAS NOT INDICATED
 ON ANY PLANS HOW THIS UNIT WILL ATTACH TO THE MWFRS.
 THE ENGINEER HAS PROVIDED (PERMIT SET OF DRAWINGS)
 DETAILS ON SHEET S6 FOR THE ATTACHMENT OF THE RTU'S
 CURB TO THE MWFRS AND THE CLIP SYSTEM FOR MOUNTING THE
 RTU TO THE CURB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  