| 2016-01-15 11:40:31 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15110411 |
| | W. P. B. PERMIT; 14120130 |
| | ADD: 1901 S. DIXIE HWY |
| | CONT: SISCA CONSTRUCTION |
| | TEL: 561-846-1179 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: SAT. NOV. 14/2014 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1) 2ND REQUEST. SHEET R-2 SHOWS THE USE OF A MINI-PAKT |
| | CONDENSING UNIT FOR ROOF TOP USE. IN DETAIL C/R-2 |
| | SECTION A-A THE DETAIL SHOWS THE USE OF A 2X6 BUILT UP |
| | CURB. THIS DETAIL IS NOT FOR A RTU DOWN UNIT WHERE |
| | THERE WOULDBE NO ROOFING MATERIAL BENEATH IT. IT WOULD |
| | APPEAR 2 SLEEPERS OR CURBS WOULD BE REQUIRED PLACED IN |
| | PARALLELL WHERE WOULD BE ROOFING BENEATH IT. |
| | |
| | 2ND REQUEST. PLEASE REVIEW SECTION 1509.7 OF THE 2010 |
| | FBC-B. 1509.7 MECHANICAL UNITS. |
| | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| | TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED |
| | MECHANICAL UNITS |
| | |
| | 2ND REQUEST. OF THE PERMITED SET OF DRAWINGS SHEET A4.0 |
| | ONLY SHOWS THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH |
| | S3 & M1.3 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE |
| | 3 RTU'S AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS |
| | A NOTE THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL |
| | LOCATIN SHALL BE DETERMINED BY OWNER/ ARCHITECT. |
| | REVISION # 15090594 DOES NOT SHOW A REVISION TO THE |
| | ROOF PLAN NOR WAS SHEET S3 UPDATED TO SHOW NEW |
| | LOCATIONS, SHEET M1.3 DOES SHOW ON THE MECHANICAL ROOF |
| | TOP SHEET A REVISION SHOWING THE LOCATION FOR 3 NEWLY |
| | LOCATED, (NOT HIGHLIGHTED SHOWING A REVISION), ROOF TOP |
| | CU UNITS, NO DETAILS UNDER MECHANICAL NOR STRUCTURAL |
| | SHEETS!!!!! |
| | |
| | 2ND REQUEST. THE STRUCTURAL ENGINEER HAS NOT INDICATED |
| | ON ANY PLANS HOW THIS UNIT WILL ATTACH TO THE MWFRS. |
| | THE ENGINEER HAS PROVIDED (PERMIT SET OF DRAWINGS) |
| | DETAILS ON SHEET S6 FOR THE ATTACHMENT OF THE RTU'S |
| | CURB TO THE MWFRS AND THE CLIP SYSTEM FOR MOUNTING THE |
| | RTU TO THE CURB. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |