2015-11-16 16:01:341ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15110411
 MASTER #14120130
  
 1) SUBMIT A REVISED M1.3 PLAN SHEET SHOWING THE
 LOCATION OF THE COLDZONE MINI-PAK ROOFTOP UNIT.
 2) SUBMIT A REVISED S3 SHEET SHOWING THE ROOFTOP
 LOCATIONS OF THE COLDZONE MINI-PAK UNIT, AND THE
 WALK-IN COOLER AND FREEZER CONDENSERS.
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 MINI-PAK AND THE CONDENSERS TO THE ROOF STRUCTURE-
 SECTION 301.12 FBC-10 MECHANICAL. PLEASE NOTE THAT THE
 COLDZONE SUBMITTAL DOES NOT PROVIDE WIND LOAD DESIGN
 CRITERIA OR STRUCTURAL DETAILS.
 4) THE SUBMITTED COLDZONE SPECS SHOW A 6" HIGH CURB
 BASE FOR SUPPORT OF THE MINI-PAK ON THE ROOF. PLEASE
 SEE SECTION 1509.7 FBC-10 BUILDING- CURBS SHALL BE
 RAISED MINIMUM 8" ABOVE THE ROOF SURFACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER