| Notes |
| Date |
Text |
| 2015-11-16 16:01:34 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION #15110411 | | | MASTER #14120130 | | | | | | 1) SUBMIT A REVISED M1.3 PLAN SHEET SHOWING THE | | | LOCATION OF THE COLDZONE MINI-PAK ROOFTOP UNIT. | | | 2) SUBMIT A REVISED S3 SHEET SHOWING THE ROOFTOP | | | LOCATIONS OF THE COLDZONE MINI-PAK UNIT, AND THE | | | WALK-IN COOLER AND FREEZER CONDENSERS. | | | 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE | | | MINI-PAK AND THE CONDENSERS TO THE ROOF STRUCTURE- | | | SECTION 301.12 FBC-10 MECHANICAL. PLEASE NOTE THAT THE | | | COLDZONE SUBMITTAL DOES NOT PROVIDE WIND LOAD DESIGN | | | CRITERIA OR STRUCTURAL DETAILS. | | | 4) THE SUBMITTED COLDZONE SPECS SHOW A 6" HIGH CURB | | | BASE FOR SUPPORT OF THE MINI-PAK ON THE ROOF. PLEASE | | | SEE SECTION 1509.7 FBC-10 BUILDING- CURBS SHALL BE | | | RAISED MINIMUM 8" ABOVE THE ROOF SURFACE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|