Plan Review Notes
Plan Review Notes For Permit 15110411
Permit Number 15110411
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-24 09:29:03IN ADDITION TO THE ALREADY MENTIONED COMMENTS FROM THE
 MECHANICAL & BUILDING REVIEWS, SPEC SHEETS INDICATING
 MINIMUM LOAD AND MAX OCP SHALL BE PROVIDED. NEC 210 .63
 REQUIRES THAT THERE BE A 15 20 AMP 125 VOLT GFCI
 SERVICE OUTLET WITHIN 25' OF THE UNIT.