| Notes |
| Date |
Text |
| 2015-11-24 09:29:03 | IN ADDITION TO THE ALREADY MENTIONED COMMENTS FROM THE | | | MECHANICAL & BUILDING REVIEWS, SPEC SHEETS INDICATING | | | MINIMUM LOAD AND MAX OCP SHALL BE PROVIDED. NEC 210 .63 | | | REQUIRES THAT THERE BE A 15 20 AMP 125 VOLT GFCI | | | SERVICE OUTLET WITHIN 25' OF THE UNIT. |
|