Plan Review Notes
Plan Review Notes For Permit 15110411
Permit Number 15110411
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-14 08:06:51BUILDING PLAN REVIEW
 W. P. B. REVISION: 15110411
 W. P. B. PERMIT; 14120130
 ADD: 1901 S. DIXIE HWY
 CONT: SISCA CONSTRUCTION
 TEL: 561-846-1179
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: SAT. NOV. 14/2014
 ACTION: DENIED
  
 1) SHEET R-2 SHOWS THE USE OF A MINI-PAKT CONDENSING
 UNIT FOR ROOF TOP USE. IN DETAIL C/R-2 SECTION A-A THE
 DETAIL SHOWS THE USE OF A 2X6 BUILT UP CURB. THIS
 DETAIL IS NOT FOR A RTU DOWN UNIT WHERE THERE WOULDBE
 NO ROOFING MATERIAL BENEATH IT. IT WOULD APPEAR 2
 SLEEPERS OR CURBS WOULD BE REQUIRED PLACED IN PARALLELL
 WHERE WOULD BE ROOFING BENEATH IT.
  
 PLEASE REVIEW SECTION 1509.7 OF THE 2010 FBC-B. 1509.7
 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
 TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS
  
 OF THE PERMITED SET OF DRAWINGS SHEET A4.0 ONLY SHOWS
 THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH S3 & M1.3
 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE 3 RTU'S
 AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS A NOTE
 THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL LOCATIN
 SHALL BE DETERMINED BY OWNER/ ARCHITECT. REVISION #
 15090594 DOES NOT SHOW A REVISION TO THE ROOF PLAN NOR
 WAS SHEET S3 UPDATED TO SHOW NEW LOCATIONS, SHEET M1.3
 DOES SHOW ON THE MECHANICAL ROOF TOP SHEET A REVISION
 SHOWING THE LOCATION FOR 3 NEWLY LOCATED, (NOT
 HIGHLIGHTED SHOWING A REVISION), ROOF TOP CU UNITS, NO
 DETAILS UNDER MECHANICAL NOR STRUCTURAL SHEETS!!!!!
  
 THE STRUCTURAL ENGINEER HAS NOT INDICATED ON ANY PLANS
 HOW THIS UNIT WILL ATTACH TO THE MWFRS. THE ENGINEER
 HAS PROVIDED (PERMIT SET OF DRAWINGS) DETAILS ON SHEET
 S6 FOR THE ATTACHMENT OF THE RTU'S CURB TO THE MWFRS
 AND THE CLIP SYSTEM FOR MOUNTING THE RTU TO THE CURB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved