| Date |
Text |
| 2015-11-14 08:06:51 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15110411 |
| | W. P. B. PERMIT; 14120130 |
| | ADD: 1901 S. DIXIE HWY |
| | CONT: SISCA CONSTRUCTION |
| | TEL: 561-846-1179 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: SAT. NOV. 14/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET R-2 SHOWS THE USE OF A MINI-PAKT CONDENSING |
| | UNIT FOR ROOF TOP USE. IN DETAIL C/R-2 SECTION A-A THE |
| | DETAIL SHOWS THE USE OF A 2X6 BUILT UP CURB. THIS |
| | DETAIL IS NOT FOR A RTU DOWN UNIT WHERE THERE WOULDBE |
| | NO ROOFING MATERIAL BENEATH IT. IT WOULD APPEAR 2 |
| | SLEEPERS OR CURBS WOULD BE REQUIRED PLACED IN PARALLELL |
| | WHERE WOULD BE ROOFING BENEATH IT. |
| | |
| | PLEASE REVIEW SECTION 1509.7 OF THE 2010 FBC-B. 1509.7 |
| | MECHANICAL UNITS. |
| | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| | TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED |
| | MECHANICAL UNITS |
| | |
| | OF THE PERMITED SET OF DRAWINGS SHEET A4.0 ONLY SHOWS |
| | THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH S3 & M1.3 |
| | BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE 3 RTU'S |
| | AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS A NOTE |
| | THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL LOCATIN |
| | SHALL BE DETERMINED BY OWNER/ ARCHITECT. REVISION # |
| | 15090594 DOES NOT SHOW A REVISION TO THE ROOF PLAN NOR |
| | WAS SHEET S3 UPDATED TO SHOW NEW LOCATIONS, SHEET M1.3 |
| | DOES SHOW ON THE MECHANICAL ROOF TOP SHEET A REVISION |
| | SHOWING THE LOCATION FOR 3 NEWLY LOCATED, (NOT |
| | HIGHLIGHTED SHOWING A REVISION), ROOF TOP CU UNITS, NO |
| | DETAILS UNDER MECHANICAL NOR STRUCTURAL SHEETS!!!!! |
| | |
| | THE STRUCTURAL ENGINEER HAS NOT INDICATED ON ANY PLANS |
| | HOW THIS UNIT WILL ATTACH TO THE MWFRS. THE ENGINEER |
| | HAS PROVIDED (PERMIT SET OF DRAWINGS) DETAILS ON SHEET |
| | S6 FOR THE ATTACHMENT OF THE RTU'S CURB TO THE MWFRS |
| | AND THE CLIP SYSTEM FOR MOUNTING THE RTU TO THE CURB. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |