Plan Review Notes
Plan Review Notes For Permit 15110395
Permit Number 15110395
Review Stop B
Sequence Number 2
Notes
Date Text
2016-01-29 18:21:56BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED
 ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED
 ASSEMBLIES.
  
 C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
  
 2- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS.