Plan Review Notes
Plan Review Notes For Permit 15110395
Permit Number 15110395
Review Stop R
Sequence Number 1
Notes
Date Text
2015-12-03 10:37:121- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) FLAT ROOF ABOVE STAIR HALL TOWER. AND, CLEARLY
 IDENTIFY SELECTED ASSEMBLY. NOTE: IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED TO MEET
 THE DESIGN PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 B) CONCRETE ROOF TILE AS SPECIFIED ON PLANS.
  
 C) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL
 BE REQUIRED.
  
 D) RTU 100 SELF ADHESIVE ROOF TILE UNDERLAYMENT AS
 SPECIFIED ON THE TYP. 2 STORY WALL SECTION ON SHEET
 A-4.
  
 E) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL SUBMITTED FOR
 LISTED ADHESIVES.
  
 2- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE:
 THERE ARE SOME PRODUCT APPROVALS SUBMITTED THAT DON'T
 HAVE THE ARCHITECT'S APPROVAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE ANY REVISED DRAWING. SUBMIT OLD
 COPIES FOR REFERENCE. PLEASE DON"T STAPLE OLD DRAWINGS
 TO NEW SET OF PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]