| 2015-12-03 10:37:12 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FLAT ROOF ABOVE STAIR HALL TOWER. AND, CLEARLY |
| | IDENTIFY SELECTED ASSEMBLY. NOTE: IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES, THEN SIGNED AND |
| | SEALED RAS 117 CALCULATIONS WILL BE REQUIRED TO MEET |
| | THE DESIGN PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | B) CONCRETE ROOF TILE AS SPECIFIED ON PLANS. |
| | |
| | C) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED |
| | TILE AS SPECIFIED ON PLANS. AND, IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. |
| | R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL |
| | BE REQUIRED. |
| | |
| | D) RTU 100 SELF ADHESIVE ROOF TILE UNDERLAYMENT AS |
| | SPECIFIED ON THE TYP. 2 STORY WALL SECTION ON SHEET |
| | A-4. |
| | |
| | E) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. SEE ROOF TILE PRODUCT APPROVAL SUBMITTED FOR |
| | LISTED ADHESIVES. |
| | |
| | 2- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: |
| | THERE ARE SOME PRODUCT APPROVALS SUBMITTED THAT DON'T |
| | HAVE THE ARCHITECT'S APPROVAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REMOVE ANY REVISED DRAWING. SUBMIT OLD |
| | COPIES FOR REFERENCE. PLEASE DON"T STAPLE OLD DRAWINGS |
| | TO NEW SET OF PLANS. |
| | |