| Plan Review Notes For Permit 15110395 |
| Permit Number |
15110395 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-07 15:34:12 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | PHIL PETTY | | | 561-805-6742 | | | [email protected] | | | | | | | | | GENERAL NOTE # 5 SAYS THAT CONDUCTOR INSULATION IS THHN | | | AND HOW ABOUT FOR OUTSIDE WIRING ? ( THWN ) | | | | | | GENERAL NOTE # 13 SAYS 50 % OFF ALL LAMPS SHOULD BE | | | HIGH EFFICIENCY , HOWEVER FBC ENERGY CODE SAYS | | | R404.1 LIGHTING EQUIPMENT (MANDATORY). | | | A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH | | | EFFICACY LAMPS. | | | | | | PLEASE SHOW EXISTING LOCATIONS OF SERVICE EQUIPMENT AND | | | PROVIDE LOAD CALCULATIONS TO VERIFY CAPACITY. | | | | | | A/C DISCONNETCS SEEM TO BE DRAWN BEHIND UNIT VERIFY NEC | | | 110.26 A WORKING SPACE CLEARANCES. | | | | | | |
|