| 2015-12-02 10:39:25 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | 1-BRING REVISED PLANS TO PALM BEACH COUNTY (2300 N. JOG |
| | RD.) FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| | DEVELOPMENT CODE. |
| | |
| | 2- THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". |
| | REVISE THE WIND DESIGN BASIS AND DESIGN PRESSURES SHOWN |
| | ON SHEET A-4. AND, REVISE ALL DOORS AND WINDOWS DESIGN |
| | PRESSURES SHOWN ON ALL EXTERIOR ELEVATIONS. SEC. |
| | R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 3- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE: SHEET E-1 |
| | SHOWS 1 CARBON MONOXIDE ALARM/SMOKE DETECTOR |
| | COMBINATION ALARM BY THE ENTRANCE OF THE FLEX ROOM. |
| | THIS ALARM IS NOT WITHIN 10 FEET OF THE BEDROOM. ALSO, |
| | NEED TO SPECIFY CARBON MONOXIDE ALARMS FOR THE OTHER |
| | SLEEPING ROOM IN THE REST OF THE HOUSE. |
| | |
| | 5- SECOND FLOOR WINDOW LOCATED AT THE NORTH EAST SIDE |
| | OF THE FLEX ROOM NEEDS TO COMPLY WITH THE WINDOW FALL |
| | PROTECTION REQUIREMENTS OF SEC. R312.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE. AND, |
| | REVISE BUILDING SECTION A ON SHEET A-3 ACCORDINGLY. |
| | |
| | 6- SECTION DETAIL #2 ON SHEET A-4: PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS FOR THE GUARDRAIL ON THE |
| | SECOND FLOOR DECK SHOWING COMPLIANCE WITH THE LIVE LOAD |
| | REQUIREMENTS OF TABLE R301.5 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). SPECIFY FASTENING OF ALL POSTS, |
| | RAILINGS AND PICKETS. NOTE: SAME COMMENTS APPLIES TO |
| | HANDRAILS AND GUARDRAIL ON THE STAIR HALL. AND, INCLUDE |
| | THE OPENING LIMITATIONS SEC. R312.1.3 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 7- TYPICAL 2 STORY WALL SECTION ON SHEET A-4: |
| | A) DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. NOTE: IF |
| | SPECIFYING NAILS OR SCREWS, THEN SPECIFY NUMBER AND |
| | SIZE. |
| | |
| | B) SPECIFY INSULATION BETWEEN GARAGE AND SECOND FLOOR. |
| | COORDINATE WITH THE ENERGY CALCULATIONS. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) PROVIDE SPECIFICATIONS FOR THE DWELLING/GARAGE FIRE |
| | SEPARATION AS REQUIRED BY SEC. R302.6 AND TABLE R302.6 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | D) SPECIFY THE FOOTING HEIGHT ABOVE THE FINISHED GRADE |
| | AS REQUIRED BY SEC. R404.1.6 AND FOOTING MIN. DEPTH AS |
| | REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | NOTE: FOOTING SIZE SPECIFIED ON THE RIGHT HAND SIDE OF |
| | THE FOOTING DOESN'T MATCH THE 1'-6" DIMENSION SHOWN ON |
| | THE SAME DRAWING. ALSO, COORDINATE SIZE WITH SIZES |
| | SPECIFIED ON SHEET S-1 TO AVOID CONFLICTS OR DELAYS. |
| | |
| | 8- ROOF FRAMING NOTES ON SHEET A-5: REVISE THE ATTIC |
| | LIVE LOAD (TRUSS BOTTOM CHORD LIVE LOAD) TO COMPLY WITH |
| | FOOTNOTES "B" AND "G" OF TABLE R301.5 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 9- REVISE ROOF SHEATHING SPECIFICATION ON SHEET A-5: |
| | NEED TO SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY |
| | SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 10- STAIR CROSS SECTION #6 ON SHEET A-5: |
| | A) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) CLARIFY NUMBER OF STRINGERS REQUIRED FOR THE STAIR |
| | CONSTRUCTION. 2 STRINGERS OR 3?. SAME DRAWING CALLS FOR |
| | 2 ON ONE PLACE AND CALLS FOR 3 ON ANOTHER PLACE. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 11- ROOF DETAIL #8 ON SHEET A-5: REVISE ROOF SLOPE TO |
| | COMPLY WITH SEC. R905.9.1 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 12- SPECIFY 7/8" MIN. STUCCO THICKNESS ON THE NEW TO |
| | EXISTING WALL SECTION #1 ON SHEET A-5 AS REQUIRED BY |
| | TABLE R702.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 13- SHEET S-1: COORDINATE FOOTING SIZE SPECIFIED ON |
| | "THE 4'' CONCRETE SLAB ON GRADE NOTES", DETAIL #4 AND |
| | FOUNDATION TYPE SIZES. SIZES DON'T MATCH. ALSO, |
| | COORDINATE WITH ITEM #7(D) ABOVE. |
| | |
| | 14- NORTH ARROW SHOWN ON FLOOR PLANS ON SHEET A-1 IS |
| | INCORRECT. REVISE AS REQUIRED TO MATCH ACTUAL NORTH |
| | ORIENTATION. SEE SURVEY FOR CORRECT NORTH ARROW |
| | ORIENTATION. NOTE: THIS IS CAUSING THE ENERGY |
| | CALCULATIONS AND A/C EQUIPMENT SIZING CALCULATIONS TO |
| | BE INCORRECT AS WELL. SEC. R103.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | 15- REVISE ENERGY CALCULATIONS: |
| | A) REVISE ORIENTATION OF BUILDING. SEE COMMENT # 14 |
| | ABOVE. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | B) NUMBER OF BEDROOMS SHOWN ON ITEM #4 IS NOT CLEAR. |
| | WHY BEDROOMS IN ADDITION IS "0"?. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) CLIMATE ZONE SHOWN ON PAGE 2 OF 4 IS INCORRECT. SEE |
| | TABLE R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014) AND REVISE AS REQUIRED. |
| | |
| | D) SLAB ON GRADE INFORMATION ON ITEM #8 IS NOT CLEAR. |
| | WHERE IS THE 200 S.F. TAKEN FROM?. WHY THIS DIMENSION |
| | IS NOT TAKEN AS LINEAR FT?. WHY IS 32 LINEAR FT ON PAGE |
| | 2 OF 4?. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | E) WINDOWS AREA AND OVERHANG DEPTH AND SEPARATION DON'T |
| | MATCH PLANS. REVISE AS REQUIRED TO MATCH. SEC. R103.2 |
| | OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | F) WHY THE GARAGE FLOOR AREA AND CEILING AREA SHOWN ON |
| | PAGE 3 OF 4 DON'T MATCH. THERE IS A BIG DIFFERENCE. |
| | SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | G) PROVIDE THE NAME OF THE BUILDER ON TOP OF FORM. |
| | |
| | ***NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE |
| | U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY |
| | CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS |
| | ARE NOT USING THE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FLAT ROOF ABOVE STAIR HALL TOWER. AND, CLEARLY |
| | IDENTIFY SELECTED ASSEMBLY. NOTE: IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES, THEN SIGNED AND |
| | SEALED RAS 117 CALCULATIONS WILL BE REQUIRED TO MEET |
| | THE DESIGN PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | B) CONCRETE ROOF TILE AS SPECIFIED ON PLANS. |
| | |
| | C) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED |
| | TILE AS SPECIFIED ON PLANS. AND, IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. |
| | R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL |
| | BE REQUIRED. |
| | |
| | D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | E) RTU 100 SELF ADHESIVE ROOF TILE UNDERLAYMENT AS |
| | SPECIFIED ON THE TYP. 2 STORY WALL SECTION ON SHEET |
| | A-4. |
| | |
| | F) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. SEE ROOF TILE PRODUCT APPROVAL SUBMITTED FOR |
| | LISTED ADHESIVES. |
| | |
| | G) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON ALL DETAILS AND SECTIONS. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT |
| | APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR ON |
| | PLANS. |
| | |
| | H) FRENCH DOORS WITH SIDELITES NOA 15-0528.24 |
| | SUBMITTED. THERE ARE TWO DIFFERENT TABLES. ONE REQUIRES |
| | REINFORCEMENT AND THE OTHER DOESN'T. CLEARLY MARK DOORS |
| | TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301. |
| | |
| | I) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT |
| | THE STAIR HALL. DRAWINGS SUBMITTED WITH FLORIDA PRODUCT |
| | APPROVAL FL14569-R5 ARE FOR 6'-8" DOORS. NEED 8'-0" |
| | DOORS. |
| | |
| | 17- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: |
| | THERE ARE SOME PRODUCT APPROVALS SUBMITTED THAT DON'T |
| | HAVE THE ARCHITECT'S APPROVAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REMOVE ANY REVISED DRAWING. SUBMIT OLD |
| | COPIES FOR REFERENCE. PLEASE DON"T STAPLE OLD DRAWINGS |
| | TO NEW SET OF PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |