| Plan Review Notes For Permit 15110375 |
| Permit Number |
15110375 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-21 15:24:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. REVISE PLAN TO INCLUDE THE CHANGE OF OCCUPANCY FROM | | | S2 (PERMIT 05020247) TO BUSINESS OCCUPANCY, FBC 107. | | | | | | 2. FBC 2014 ACCESSIBILITY TABLE 404.2.4.1, 18IN | | | MANEUVERING CLEARANCE REQUIRED FOR DOORS 01 AND 02, | | | PULL SIDE. | | | | | | 3. SEE PAGE A0.01 OF PERMIT #05020247. SHEET CVR | | | SUBMITTED DECLARES A IIIB BUILDING TYPE, BUT THE | | | BUILDING WAS CONSTRUCTED AS TYPE V. A TYPE IIIB | | | REQUIRES 2 HOUR EXTERIOR WALLS. | | | | | | THE WEST WALL IS A 1 HOUR RATED WALL BASED ON DISTANCE | | | TO ASSUMED PROPERTY LINE. PLEASE REVISE BUILDING TYPE | | | TO TYPE V OR SHOW COMPLIANCE WITH TYPE IIIB BUILDING | | | TYPE (TABLE 601, 602, 705.8). | | | | | | 4. USE OF MEZZANINE IS NOT CLEAR. SEE FBC 2014 | | | ACCESSIBILITY 201.1.1 AND REVISE PLAN TO INCLUDE | | | EXCEPTION TO VERTICAL ACCESSIBILITY (OR PROVIDE | | | VERTICAL ACCESSIBILITY). | | | | | | | | | |
|