| 2016-02-22 17:36:43 | 2ND ELECTRICAL REVIEW NOTES FOR PERMIT #: 15110245, |
| | 15110318, 15110330, 15110346, 15110351, 15110356 & |
| | 15110362 |
| | REVIEWED FOR COMPLIANCE WITH: FBC 5TH EDITION 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | SHEET A-E 1 COMMENT #9: I MENTIONED THE NEED FOR A |
| | SECOND WALL SWITCH FOR THE LOCATIONS WHERE YOU INTEND |
| | TO HANG A PADDLE FAN. YOUR RESPONSE ONLY CONFIRMS THAT |
| | THERE WILL BE A PADDLE FAN W/A LIGHT KIT. NEC |
| | 210.70(A)(1) MANDATES THAT BE AT LEAST ONE WALL SWITCH |
| | CONTROLLED LUMINAIRE IN EVERY HABITABLE ROOM, THEREFORE |
| | IF YOU WILL NOT BE ADDING THE SECOND SWITCH, YOU SHALL |
| | MAKE SURE THAT THE SWITCH CONTROLS THE LUMINAIRE AND |
| | NOT THE FAN. |
| | |
| | SHEET B-E 1 COMMENT #10: SAME AS ABOVE. |
| | |
| | SHEET C-E 1 DIDN?T HAVE THE ABOVE COMMENT MENTIONED BUT |
| | THE REQUIREMENT APPLIES AS WELL. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |