| 2015-11-12 09:10:14 | SUBMITTAL DENIED |
| | 2010 FBC |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ELEVATION CERTIFICATE THAT WAS SUBMITTED SHOWS |
| | THAT THE PROJECT IS IN VIOLATION OF THE CITY OF WEST |
| | PALM BEACH'S FLOOD ORDINANCE AND FEMA REQUIREMENTS FOR |
| | CONSTRUCTION IN A SPECIAL FLOOD HAZARD AREA. BASED ON |
| | THE ELEVATION CERTIFICATE FOR FINISHED CONSTRUCTION |
| | THAT WAS SUBMITTED, THE REQUIREMENTS OF APPROVED PLANS |
| | FOR THE ADDITION OF A SECOND FLOOR ABOVE THE EXISTING |
| | GARAGE (#14011176) AND THE REVISION TO ADD THE TWO |
| | STORY ADDITION BETWEEN THE GARAGE AND THE DWELLING |
| | (#15050172) HAVE NOT BEEN COMPLIED WITH. |
| | |
| | 2) PER THE APPROVED PLANS, THE EXISTING FIRST FLOOR |
| | GARAGE AND THE ONE CAR GARAGE ON THE FIRST FLOOR OF THE |
| | TWO STORY ADDITION ARE BELOW THE REQUIRED DESIGN FLOOD |
| | ELEVATION OF 7.5 FEET NGVD AND ARE REQUIRED TO HAVE |
| | FLOOD OPENINGS. ONLY FLOOD RESISTANT MATERIALS AND |
| | EQUIPMENT CAN BE INSTALLED BELOW THE 7.5 FEET DFE. THE |
| | CITY OF WEST PALM BEACH'S FLOOD ORDINANCE AND FEMA |
| | REQUIRE THAT THESE AREAS CAN ONLY BE USED FOR THE |
| | PARKING OF VECHICLES, BUILDING ACCESS AND STORAGE |
| | (LOW-VALUE ITEMS). |
| | |
| | 3) THE ELEVATION CERTIFICATE INDICATES THAT THE FORMER |
| | GARAGE (ELEVATION 5.6 FEET) IS A PERSONAL GYM AND THAT |
| | THERE IS EQUIPMENT SERVICING THE BUILDING THAT IS BELOW |
| | THE REQUIRED DESIGN FLOOD ELEVATION OF 7.5 FEET NGVD. |
| | |
| | 4) THE ELEVATION CERTIFICATE IS REQUIRED TO INCLUDE |
| | PHOTOGRAPHS OF THE FLOOD OPENINGS OR VENTS. |
| | |
| | |