| Plan Review Notes For Permit 15110258 |
| Permit Number |
15110258 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-11-13 18:47:10 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE RAS 117 CALCULATIONS ARE INCORRECT. THE VULT | | | WINDSPEED FOR RISK CATEGORY IV FOR THIS BUILDING IS | | | GREATER THAN 170MPH. SEE WIND SPEED MAP FIGURE 1609B IN | | | THE FBC-BUILDING, 5TH EDITION (2014). THE FASTER WIND | | | SPEED WILL CREATE INCREASED DESIGN PRESSURES. THE THREE | | | ENHANCED FASTENING DOCUMENTS THAT WERE SUBMITTED ALL | | | HAVE THE SAME ROOF ZONE PRESSURES SPECIFIED, HOWEVER, | | | THE LAP SPACING WAS DECREASED. PLEASE REVISE THE | | | DOCUMENTS TO COMPLY WITH THE 2014 FBC. | | | | | | |
|