2015-11-12 13:29:47RE-ROOF SECOND BUILDING REVIEW CHECKLIST.COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 A) THE RISK CATEGORY IS INCORRECT. SEE TABLE 1604.5 OF
 FBC-BUILDING, 5TH EDITION (2014) AND REVISE AS
 REQUIRED. REVISE DESIGN PRESSURES ACCORDINGLY.
 RESPONSE: THE SELECTED RISK CATEGORY IS INCORRECT
 AGAIN. THIS IS A HOSPITAL. THIS IS NOT RISK CATEGORY
 III. THE WIND VELOCITY AND DESIGN DESIGN PRESSURES NEED
 TO BE REVISED ACCORDINGLY ALSO. ENGINEER TO REVIEW
 FIGURE 1609B OF FBC-BUILDING, 5TH EDITION (2014) AND
 REVISE ULTIMATE DESIGN WIND SPEED AND DESIGN PRESSURES
 ACCORDINGLY.
  