| Plan Review Notes For Permit 15110258 |
| Permit Number |
15110258 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-12 13:29:47 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST.COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | | SUBMITTED: | | | A) THE RISK CATEGORY IS INCORRECT. SEE TABLE 1604.5 OF | | | FBC-BUILDING, 5TH EDITION (2014) AND REVISE AS | | | REQUIRED. REVISE DESIGN PRESSURES ACCORDINGLY. | | | RESPONSE: THE SELECTED RISK CATEGORY IS INCORRECT | | | AGAIN. THIS IS A HOSPITAL. THIS IS NOT RISK CATEGORY | | | III. THE WIND VELOCITY AND DESIGN DESIGN PRESSURES NEED | | | TO BE REVISED ACCORDINGLY ALSO. ENGINEER TO REVIEW | | | FIGURE 1609B OF FBC-BUILDING, 5TH EDITION (2014) AND | | | REVISE ULTIMATE DESIGN WIND SPEED AND DESIGN PRESSURES | | | ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|