| Notes |
| Date |
Text |
| 2015-11-09 18:40:59 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | | SUBMITTED: | | | A) THE RISK CATEGORY IS INCORRECT. SEE TABLE 1604.5 OF | | | FBC-BUILDING, 5TH EDITION (2014) AND REVISE AS | | | REQUIRED. REVISE DESIGN PRESSURES ACCORDINGLY | | | | | | B) THE FASTENER SPACING SPECIFIED DOESN'T MATCH | | | SELECTED SYSTEM W-39. REVISE AS REQUIRED TO MATCH. | | | ALSO, REVISE FASTENER SPACING FOR ROOF ZONES 2 AND 3 | | | ACCORDINGLY. SEC. 1609 FBC BUILDING, 5TH EDITION | | | (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|