2015-11-09 18:40:59RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 A) THE RISK CATEGORY IS INCORRECT. SEE TABLE 1604.5 OF
 FBC-BUILDING, 5TH EDITION (2014) AND REVISE AS
 REQUIRED. REVISE DESIGN PRESSURES ACCORDINGLY
  
 B) THE FASTENER SPACING SPECIFIED DOESN'T MATCH
 SELECTED SYSTEM W-39. REVISE AS REQUIRED TO MATCH.
 ALSO, REVISE FASTENER SPACING FOR ROOF ZONES 2 AND 3
 ACCORDINGLY. SEC. 1609 FBC BUILDING, 5TH EDITION
 (2014).
  