| Plan Review Notes For Permit 15110253 |
| Permit Number |
15110253 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-10 11:11:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. APPLICATION IS TO INCLUDE THE FOLLOWING BASIC | | | INFORMATION FOR REROOFS: MEAN ROOF HEIGHT, ROOF PITCH, | | | DECK TYPE, TYPE OF ROOF PROPOSED. "38 SQ REROOF" IS NOT | | | AN ADEQUATE DESCRIPTION AND PACKAGE INCLUDED ONLY A | | | ROOF PLAN (NO PITCH OR OTHER INFORMATION). | | | | | | 2. ROOF PLAN SHOWS SKYLIGHTS BUT DOES NOT STATE THAT | | | THEY WILL BE REPLACED OR IF THEY WILL REMAIN. IF | | | REPLACING, A PRODUCT APPROVAL IS REQUIRED FAC9N-3. | | | | | | 3. ON THE ROOF TILE PRODUCT APPROVAL, INDICATE METHOD | | | OF FASTENING PROPOSED (DIRECT DECK AND DECK THICKNESS | | | OR BATTENS, FASTENERS). THIS INFORMATION IS REQUIRED | | | FOR RAS127 CALCULATIONS. THE CALCULATION WILL BE DONE | | | FOR YOU BUT CANNOT BE DONE WITHOUT BASIC INFORMATION | | | REGARDING THE INSTALLATION. | | | | | | 4. IF ADHESIVE IS PROPOSED FOR FASTENING, PROVIDE THE | | | PRODUCT APPROVAL AND INDICATE PADDY SIZE PROPOSED. | | | | | | 5. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. | | | | | | |
|