| 2016-02-02 10:45:08 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110125 |
| | ADD: 114 S. OLIVE AVE. |
| | CONT: HOOD DEPOT |
| | TEL: 954-570-9860 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: WED. DEC. 30/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | |
| | |
| | 1) COMPLILED. WIND DESIGN CRITERIA ON THE PLANS. |
| | |
| | |
| | 2A)(1) 3RD REQUEST. SEMI COMPLIED. PRECISION ALUMINUM |
| | PRODUCTS/ A/C STANDS SUBMITTED ENGINEERING FROM FRANK |
| | BENNARDO NO COVERE SHEETS WERE PROVIDED INDICATING THIS |
| | IS A FLORIDA APPROVAL OR A MIAMI-DADE NOA. |
| | |
| | 2A)(2) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS |
| | AND ROOF TOP STAND AND ROOF TOP CURBS INTAKE AND |
| | EXHAUST FANS PLEASE PROVIDE EITHER A FLORIDA APPROVAL |
| | OR MIAMI-DADE NOA. . PLEASE SHOW COMPLIANCE WITH: |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOF TOP CURBS, ROOF TOP INTAKE & EXHAUST FANS |
| | -NO PRODUCT APPROVALS WERE SUBMITTED!!!! |
| | (31)(G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2B) 3RD REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3) 3RD REQUEST.THE ENGINEER OF RECORD (STRUCTURAL) HAS |
| | NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR |
| | AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND |
| | APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| | THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |