| Date |
Text |
| 2016-01-14 14:42:43 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED |
| | DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL |
| | REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED |
| | BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO |
| | SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE |
| | REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION |
| | OF ANY PREVIOUS COMMENTS. |
| | |
| | 1. THIS TIME THE MASTER PERMIT REFERRED TO ON THE |
| | APPLICATION IS FOR THE COMMERCIAL REMODEL OF THE BLDG. |
| | BUT THE KITCHEN HOOD SYSTEM SPECIFIED ON THE MASTER |
| | PERMIT DIFFERS FROM THE ONE BEING PROPOSED ON THIS |
| | APPLICATION THEREFORE ALL ELECTRICAL REQUIREMENTS AS |
| | PREVIOUSLY REQUESTED SHALL BE SUBMITTED FOR REVIEW. |
| | 2. THE SYSTEM ON THE MASTER PERMIT IS A CAPTIVE AIR AND |
| | THIS IS A HOOD DEPOT. |
| | 3. YOU SHALL PROVIDE CIRCUIT DIRECTORY, WIRING DIAGRAM |
| | AND LOAD CALCS FOR BOTH, THE HOOD FAN MOTORS AND THE |
| | MUA COOLING SYSTEM. |
| | 4. PROVIDE SHUNT TRIP BREAKER FOR ALL ELECTRICAL |
| | EQUIPMENT AND OUTLETS UNDER THE HOOD. |
| | 5. YOU SHALL PROVIDE A CORRECTED CIRCUIT DIRECTORY FOR |
| | THE PANELS AFFECTED BY THIS MODIFICATION. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE?SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE?SUBMITTAL FORM, AS WELL AS AN |
| | INDICATION ON THE PAGE WHERE THE CORRECTION WAS |
| | PERFORMED. ADDITIONALLY, PLEASE INSERT CORRECTED PAGES |
| | INTO THE SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARISON. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. IF YOU HAVE FURTHER QUESTIONS, |
| | PLEASE DON?T HESITATE TO CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH.: 561?805?6746 |
| | EMAIL: [email protected] |
| | |