| Date |
Text |
| 2015-12-30 09:12:34 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110125 |
| | ADD: 114 S. OLIVE AVE. |
| | CONT: HOOD DEPOT |
| | TEL: 954-570-9860 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: WED. DEC. 30/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | |
| | |
| | 1) 2ND REQUEST. THE (7) MECHANICAL SHEETS SUBMITTED BY |
| | HOOD DEPOT DO NOT HAVE THE WIND DESIGN CRITERIA ON THE |
| | PLANS, |
| | |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 1.2. RISK CATEGORY. |
| | |
| | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 2A) 2ND REQUEST. SHEET 3 OF 7 SHOWS 3 ROOF TOP |
| | CONDENING UNITS AND ROOF TOP STAND AND ROOF TOP CURBS |
| | INTAKE AND EXHAUST FANS PLEASE PROVIDE EITHER A FLORIDA |
| | APPROVAL OR MIAMI-DADE NOA. . PLEASE SHOW COMPLIANCE |
| | WITH: FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(D) ROOF TOP CURBS, ROOF TOP INTAKE & EXHAUST FANS |
| | (31)(G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2B) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3) 2ND REQUEST. SHEET 6 & 7 SHOWS THE AIR COMPRESSOR |
| | BEING HUNG FROM THE SIDE OF THE THRESHOLD BUILDING. ALL |
| | THRESHOLD INSPECTIONS ARE TO BE PREFORMED BY THE |
| | THRESHOLD INSPECTOR. NO INSPECTIONS OF THIS SYSTEM HAS |
| | OCCURRED. THE SECOND ISSUE IS THE ENGINEER OF RECORD |
| | (STRUCTURAL) HAS NOT REVIEWED THESE PLANS FOR CODE |
| | COMPLIANCE, NOR AFFIXED THERE SHOP DRAWING STAMPED |
| | REVIEWED AND APPROVED. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |