| 2015-12-09 10:04:29 | 1ST REVIEW 2014 MECHANICAL |
| | PERMIT #15110125 |
| | 12/9/15 |
| | |
| | 1) THE HOOD 1A & 1B SUPPLY FAN AIR INLET (SF-1) SHALL |
| | NOT BE LOCATED IN AN ALLEY, AND NOT WITHIN THE REQUIRED |
| | 10' CLEARANCE DISTANCE TO THE ADJACENT PROPERTY LINE- |
| | REFER TO SECTIONS 508.1 AND 401.4 FBC-14 MECHANICAL. |
| | 2) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR |
| | ALL EXTERIOR FAN AND DUCT INSTALLATIONS, INCLUDING THE |
| | SUPPORT PLATFORMS AND BRACKET ASSEMBLIES IN THE ALLEY- |
| | SEE SECTION 301.5 AND PROVIDE THE WIND LOAD DESIGN |
| | CRITERIA ON THE PLANS AND COMPLETE DETAILS. PLEASE |
| | NOTE: A) SHOP DRAWINGS FOR ALL THE STRUCTURAL |
| | ASSEMBLIES SHALL BE REVIEWED AND APPROVED BY THE |
| | ENGINEER OF RECORD AND SUBMITTED TO THE BUILDING |
| | DEPARTMENT. B)WELDING CERTIFICATIONS SHALL BE ON-SITE |
| | AT TIME OF INSPECTION. |
| | 3) PROVIDE UL TESTED AND APPROVED FIRE STOPPING |
| | ASSEMBLIES ON THE PLAN FOR THE DUCTS PENETRATING THE |
| | FIRE-RATED EXTERIOR WALL. |
| | 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF ALL APPLIANCES AND EQUIPMENT AND THE MINIMUM |
| | REQUIRED CLEARANCE DISTANCES FOR EXHAUST AND VENT |
| | OUTLETS, AND MECHANICAL AND GRAVITY AIR INTAKES- REFER |
| | TO SECTIONS 401.4, 501.3.1, AND 506.3.1. PLEASE NOTE A |
| | REVISION TO THE ORIGINAL MECHANICAL ROOF PLAN SHEET |
| | SUBMITTED UNDER THE PERMIT # 13060638 MAY BE REQUIRED |
| | FOR REVIEW AND FOR PUBLIC RECORD. SEE ALSO SECTION |
| | 304.11: GUARDS MAY BE REQUIRED FOR EQUIPMENT WITHIN 10' |
| | OF A ROOF EDGE. |
| | 5) PROVIDE AIR VELOCITY CALCULATIONS FOR THE EXHAUST |
| | DUCTS- SECTION 506.3.4. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |