| 2015-12-14 13:55:39 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110125 |
| | ADD: 114 S. OLIVE AVE. |
| | CONT: HOOD DEPOT |
| | TEL: 954-570-9860 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: MON. DEC. 21/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE (7) MECHANICAL SHEETS SUBMITTED BY HOOD DEPOT DO |
| | NOT HAVE THE WIND DESIGN CRITERIA ON THE PLANS, |
| | |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 1.2. RISK CATEGORY. |
| | |
| | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 2A) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS AND |
| | ROOF TOP STAND. PLEASE SHOW COMPLIANCE WITH: FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31 (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 3) SHEET 5OF 7 SHOWS THE AIR COMPRESSOR BEING HUNG FROM |
| | THE SIDE OF THE THRESHOLD BUILDING. ALL THRESHOLD |
| | INSPECTIONS ARE TO BE PREFORMED BY THE THRESHOLD |
| | INSPECTOR. THE SECOND ISSUE IS THE ENGINEER OF RECORD |
| | HAS NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR |
| | AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND |
| | APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| | THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |