Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-30 10:06:221ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 NEC 240.24 (A) & (B) PANELS SHALL BE LOCATED SUCH THAT
 OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT OCCUPANTS
 SHALL HAVE ACCESS TO OCP DEVICES.
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
 (B) BRANCH CIRCUIT EXTENSIONS OR MODIFICATIONS ?
 DWELLING
 UNITS. IN ANY OF THE AREAS SPECIFIED IN 210.12(A),
 WHERE
 BRANCH-CIRCUIT WIRING IS MODIFIED, REPLACED, OR
 EXTENDED, THE
 BRANCH CIRCUIT SHALL BE PROTECTED BY ONE OF THE
 FOLLOWING:
 (1) A LISTED COMBINATION-TYPE AFCI LOCATED AT THE
 ORIGIN OF
 THE BRANCH CIRCUIT
 (2) A LISTED OUTLET BRANCH-CIRCUIT TYPE AFCI LOCATED AT
 THE
 FIRST RECEPTACLE OUTLET OF THE EXISTING BRANCH CIRCUIT
 (2) ISLAND COUNTERTOP SPACES. AT LEAST ONE RECEPTACLE
 SHALL BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH
 A
 LONG DIMENSION OF 600 MM (24 IN.) OR GREATER AND A
 SHORT
 DIMENSION OF 300 MM (12 IN.) OR GREATER.
  