| 2015-11-24 11:27:53 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | *************COMMENTS FOR MAIN HOUSE PLANS SUBMITTED: |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | 2- DESIGN PARAMETERS ON SHEET A-1 AND A-2: CLARIFY WHY |
| | THE DOORS AND WINDOWS POSITIVE DESIGN PRESSURES ARE |
| | HIGHER THAN THE NEGATIVE DESIGN PRESSURES. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) NEW EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | B) NEW WINDOWS AS SHOWN ON PLANS. |
| | |
| | C) HURRICANE SHUTTERS IF GLAZING IN DOORS AND WINDOWS |
| | IS NOT IMPACT GLAZING. AND, PROVIDE SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE. SEE SHUTTERS INSTALLATION CITY |
| | SAMPLE OR PROVIDE COMPLETE SHUTTERS INFORMATION ON A |
| | DIFFERENT FORMAT. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| | NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| | |
| | 4- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | ***************COMMENTS FOR DETACHED LAUNDRY ROOM: |
| | 1- PROVIDE 2 SETS OF PLANS SIGNED AND SEALED BY THE |
| | ENGINEER OF RECORD. ONLY ONE SET OF PLANS WAS |
| | SUBMITTED. SEC. 107.1 CITY AMENDMENTS. |
| | |
| | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW AWNINGS SHOWN ON FRONT AND RIGHT ELEVATIONS. OR |
| | PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT. . |
| | SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 3- DESIGN PARAMETERS ON SHEET A-1: CLARIFY WHY THE |
| | DOORS AND WINDOWS POSITIVE DESIGN PRESSURES ARE HIGHER |
| | THAN THE NEGATIVE DESIGN PRESSURES. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) NEW EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | B) HURRICANE SHUTTERS IF GLAZING IN DOORS IS NOT IMPACT |
| | GLAZING. AND, PROVIDE SHUTTERS COMPLETE INSTALLATION |
| | SCHEDULE. SEE SHUTTERS INSTALLATION CITY SAMPLE OR |
| | PROVIDE COMPLETE SHUTTERS INFORMATION ON A DIFFERENT |
| | FORMAT. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| | NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| | |
| | 4- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- REVISE DESIGN PARAMETERS ON SHEET A-1. THIS IS NOT |
| | ALTERATION LEVEL 1. THIS IS ALTERATION LEVEL 3. SEC. |
| | 505 OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | |
| | ***PLEASE PROVIDE A RESPONSE LETTER SHOWING HOW EACH |
| | ITEM WAS ADDRESSED TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE ANY REVISED SHEET. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE, BUT DON'T STAPLE THEM TO THE NEW SET OF |
| | PLANS. |
| | |