| Plan Review Notes For Permit 15110017 |
| Permit Number |
15110017 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-16 09:07:34 | PASS PROVISO | | | | | | 1) PROVIDE A DETAIL FROM THE STRUCTURAL ENGINEER ON THE | | | BOLT SIZE ANCHORING THE FANS TO EQUIPMENT SUPPORT, | | | AT FIRST INSPECTION. PER SECTION 305.15 WIND RESISTANCE | | | 2014 FBC (M) | | | 2) REFER TO SECTION 501.3.1 LOCATION OF EXHAUST | | | OUTLETS. | | | KEY NOTE # 6 PAGE M-1 2014 FBC (M) | | | 3) TEST WILL BE REQUIRED FOR STAR PRESSURIZATION DOOR | | | PULLS AND DOOR PUSH. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|