2015-12-14 12:24:072ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 1. THE PLAN IS REDUCED AND TOO SMALL TO READ AND TOO
 SMALL FOR RECORD RETENTION. PLEASE PROVIDE AN ENLARGED
 PLAN. COMMENT IS SEMI COMPLIED, ADDITIONAL PLANS ARE
 REQUIRED.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2. THE WIND DESIGN AND STRUCTURAL ATTACHMENT
 INFORMATION IS UNCLEAR AND APPEARS GENERIC. SUCH DESIGN
 MUST BE SITE SPECIFIC. PLEASE PROVIDE THE SPECIFIC
 APPLICABLE DESIGN PRESSURES AS DETERMINED USING THE
 METHODS IN FBC-R301.1.3 ENGINEERED DESIGN. PLEASE
 PROVIDE A SPECIFIC PLAN INDICATING THE LOCATION AND
 TYPE OF CONNECTORS TO BE INSTALLED. PROVIDE WIND DESIGN
 CRITERIA FOR THE SPECIFIC GEOGRAPHICAL LOCATION OF THE
 BUILDING AND CONSIDERING THE PROPOSED LOCATION OF THE
 SYSTEM ON THE BUILDING. IF DESIGN IS NOT TO BE PROVIDED
 BY A FLORIDA LICENSED ENGINEER, THEN PROVIDE STRUCTURAL
 CALCULATIONS TO JUSTIFY THE DESIGN. NOT COMPLIED
  
 YOU HAVE SUBMITTED A DESIGN USING SOFTWARE TO DEVELOP A
 LAYOUT FOR AN ARRAY WHICH SPECIFIES CERTAIN COMPONENTS
 OF A SYSTEM. THE INFORMATION IS NOT SITE SPECIFIC AND
 DOES NOT BEAR THE SEAL OF AN ENGINEER. ALTHOUGH CERTAIN
 DESIGN PARAMETERS ARE EVIDENT IN THE WIND LOAD ANALYSIS
 PLAN, SUCH AS WIND SPEED, EXPOSURE, AND BUILDING
 HEIGHT, YOU HAVE PROVIDED SOME PAGES RELATED TO SNOW
 LOADS RATHER THAN WIND LOADS FROM PART OF A GENERAL
 DESIGN ANALYSIS OF THE PRODUCT BY SML INC. PLEASE
 PROVIDE SPECIFIC WIND DESIGN PRESSURES. YOU MAY PROVIDE
 DESIGN LOADS FROM CHARTS BY THE MANUFACTURERS
 CONSULTANT ENGINEER, BUT DETERMINATION OF SYSTEM
 COMPONENTS SUCH AS CONNECTOR'S TO THE ROOF AND SPACING
 OF SUCH CONNECTOR'S SHOULD BE VERIFIED BY AN ENGINEER
 TO ASSURE THE SYSTEM DESIGN CAN WITHSTAND WIND
 PRESSURES. YOUR INCLUSION OF SNOW LOAD CHARTS IS NOT
 USEFUL. THE SPEC SHEETS PROVIDED FOR THE FLASHFOOT
 ANCHORS DO NOT SPECIFY THE LENGTH OF THE ANCHOR AND
 PROVIDES TWO POSSIBLE BOLT DIAMETERS. THE ANCHOR
 INDICATES IT IS FOR SHINGLED ROOF WHICH SUGGEST IT IS
 FOR SLOPED APPLICATIONS AND NOT FOR A FLAT ROOF AS
 PROPOSED. THE DOCUMENT FROM IRONRIDGE INDICATES THE
 2010 FBC IN IT'S CODE COMPLIANCE PAGE, THE VERSION IS
 INCORRECT.
  
  